4.14.5

Switch-On and Switch-Off Behavior

This chapter describes the switch-on and switch-off behavior of the PSD.
4.14.6

Behavior of "holding brake" function

Drives with an enabled holding brake function have a special timing for switching on and off the
output stage (➜ # 118). Events that remove the DRV.ACTIVE signal trigger the holding brake to
apply. As with all electronic circuits, the general rule applies that there is a possibility of the internal
holding brake module failing.
Functional safety, e.g. with hanging load (vertical axes), requires an additional mechanical brake
which must be safely operated, for example by a safety control.
If velocity drops below threshold CS.VTHRESH or timeout occurs during a stop procedure, the brake
is applied. Set parameter MOTOR.BRAKEIMM to 1 with vertical axes, to apply the motor holding
brake (➜ # 118) immediately after faults or Hardware Disable.
4.14.6.1
Behavior when undervoltage condition is present
The behavior in an undervoltage condition depends on the VBUS.UVMODE setting.
VBUS.UVMODE
0
1 (default)
Technical Description and Data
Rated data
Continuous regen power, external
resistor
Peak regen power, external resistor
(1s)
Absorption energy in capacitors (+/-
20%)
DC Bus Capacitance
Internal regen resistor
Continuous power, internal resistor
Peak regen power, internal resistor
(0.5s)
External regen resistor
Continuous regen power, external
resistor
Peak regen power, external resistor
(1s)
Absorption energy in capacitors (+/-
20%)
DC Bus Capacitance
DC Bus Undervoltage Mode. Consult the Workbench Online Helpfor
configuring the parameter.
The drive will report a F502 undervoltage fault any time an
undervoltage condition occurs.
The drive will report a warning n502 if not enabled. The drive will
report a fault if the drive is enabled when the condition occurs, or an
attempt is made to enable while an under voltage condition occurs.
September 2020
Units
240 V
400 V / 480 V
kW
3
6
kW
5.4
21.4
Ws
10
70 / 40
µF
470
Ohm
23
W
200
kW
7.7
30.6
Ohm
23
kW
6
12
kW
7.7
30.6
Ws
15
110 / 60
µF
680
Section 4
25