Swegon GLOBAL PX Operation And Maintenance Instructions page 38

Hide thumbs Also See for GLOBAL PX:
Table of Contents

Advertisement

External coils
Configuration of the coils
This menu will allow for the configuration of any combi-
nation of external heating and or cooling coil(s).
Setting Settings
range
Type
None
Hot water
Cold water
Hot & Cold water
Reversible water
Electric PWM
Electric PWM + Cold water
Water preheating
Water preheating+postheating
Water preheating+reversible
Electric 0...10V
Electric 0...10V + Cold water
Water post heating
The external post heating coil is delivered seperately from
the air handling unit and will not be pre configured in
factory. Both the coil and the 3-way valve will have to be
installed and wired on site. The capacity of the coil will be
controlled proportionally in order to keep a temperature
as defined by the selected operating mode. The reaction
speed can be set. A higher Setting will result in a faster
reaction speed; a lower Setting will result in a slower reac-
tion speed.
Setting
Control mode
Setpoint
Reaction Speed
Water cooling coil
The external post cooling coil is delivered seperately from
the air handling unit and will not be pre configured in
factory. Both the coil and the 3-way valve will have to be
installed and wired on site. The capacity of the coil will be
controlled proportionally in order to keep a temperature
as defined by the selected operating mode.
Setting
Control mode
Setpoint
Reaction Speed
38
Factory
setting
None
Settings
Factory
range
setting
Exhaust
Supply
Supply
0...99,9°C
21,0°C
1...10
5
Settings
Factory
range
setting
Exhaust
Supply
Supply
0...99°C
17,0°C
1...10
5
ADVANCED SETUP
BOOST
POST VENTILATION
EXTERNAL COILS
FROST PROTECTION
FREECOOLING
Electrical postheating coil
The external post heating coil is delivered seperately from
the air handling unit and will not be pre configured in fac-
tory. The coil will have to be installed and wired on site.
The capacity of the coil will be controlled proportionally
in order to keep a temperature as defined by the selected
operating mode.
Setting
Control mode
Setpoint
PID - Proportional Band
PID - Integral
PID - derivate
Combi coil
The external change over coil is delivered seperately from
the air handling unit and will not be pre configured in fac-
tory. The coil will have to be installed and wired on site.
The capacity of the coil will be controlled proportionally
in order to keep a temperature as defined by the selected
operating mode.
Setting
Activate change over
Neutral band High
Neutral band Low
Settings
Factory
range
setting
Exhaust
Supply
Supply
0...+99°C
21,0°C
0...100
5
0...100
30
0...100
11
Settings
Factory
range
setting
No
No
Yes
0...+50°C
4K
0...+50°C
2K
Operation and maintenance instructions