Eclipse TA Series Installation Manual page 29

Thermair burners
Table of Contents

Advertisement

PROBLEM
Cannot initiate a start
sequence.
POSSIBLE CAUSE
Air pressure switch has not
made contact.
High gas pressure switch has
activated.
Low gas pressure switch has
activated.
Malfunction of the flame
safeguard system (e.g., shorted-
out flame sensor or electrical
noise in the sensor line).
No power to the control unit.
Main power is off.
Eclipse ThermAir T/A Series v1.10, Installation Guide No. 114, 4/7/06
SOLUTION
Check air pressure switch
adjustment.
Check air filter.
Check blower rotation.
Check outlet pressure from
blower.
Check incoming gas pressure.
Adjust gas pressure if necessary.
Check pressure switch setting
and operation.
Have a qualified electrician
troubleshoot and correct the
problem.
Be sure the main power to the
system is switched to the "on"
position.


Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents