MOUNTING INSTRUCTIONS
Intelli-Wave inverters are designed for indoor, out of weather use only. During
operation, the inverter should be in a dry, cool and well-ventilated area as close to
the batteries as possible, but not in the same compartment as the batteries. Ensure
the inverter is away from flammable materials and fumes.
The inverter end plates include a mounting flange for easy mounting. If permanently
fixed, the inverter should be mounted to a suitable horizontal or vertical panel, with
at least 10cm clearance from the end plates to provide adequate ventilation for the
cooling fan.
6.5mm mounting holes
Part No.
Inverter Dimensions
Length
Width
Height
IP2000
478mm
250mm
105mm
6