6.2 GENERAL STIPULATIONS REGARDING UNIT PLACEMENT

• The minimum space for basic maintenance and service is dependent upon the width of
the doors as specified in the technical specifications for the given unit, or a minimum of
600 mm
• The minimum space required for repairs and the replacement of devices is the width of
the unit + 200 mm
• The minimum spacing between hot items and the unit is 200 mm.
• Units for outdoor installation must be sufficiently fastened to their base as required for
the expected climactic conditions and exposure.

6.3 PLACING UNITS ON FLOORS

• Permitted handling of units for installation is specified in Subsection 4.
• The units must be installed on solid, level floors to which they can be rigidly fastened. It
is advisable to install a dampening material (e.g. rubber, cork) under the frame of the
unit at the place of installation
• The maximum permitted deviation from the horizontal is 0.5% (0.3°)
• The unit must be installed at a sufficient height above the floor / ground to provide
sufficient trap height on chambers equipped with condensate drains, see the Subsection
6.6 TRAP ASSEMBLY.
• Failure to ensure sufficient stability or levelness of the surface may degrade the
functionality of the unit and even cause damage, including misalignment of the fan
impeller relative to the inlet fairing, the inability to open the chamber doors, etc.!

6.4 GENERAL INSTRUCTIONS FOR ASSEMBLING THE UNIT

Perform the following before installing the unit:
• Check the site of installation of the unit and the stability of all underlying surfaces:
the unit is supported over its entire footprint, the unit is installed in a level position
within the maximum allowed deviation, and the dampening material is installed
between the unit and the underlying surface or steel structure.
• All packaging film is removed from the unit
• All additional items have been removed from the unit (cardboard boxes with accessories
or control circuitry and other accessories) and placed in a secure and dry place