Table B.4 Service Menu Alarm Settings by Line ID (continued)
Line
Parameter
ID
Name
Event Delay Time (sec)
S253
Event Enabled
Event: CIRCUIT 1 LOW PRESS
Event Delay Time (sec)
S254
Event Enabled
Event: CIRCUIT 2 LOW PRESS
Event Delay Time (sec)
S255
Event Enabled
Event: CIRCUIT 1 PUMPD. FAIL
Event Delay Time (sec)
S256
Event Enabled
Event: CIRCUIT 2 PUMPD. FAIL
Event Delay Time (sec)
S257
Event Enabled
Event: DIG SCROLL1 HIGH TEMP
Event Delay Time (sec)
Event Enabled
S258
Event: DIG SCROLL2 HIGH
TEMP
Event Reset Type
Event Delay Time (sec)
S259
Event Enabled
Event: EL HEAT HIGH TEMP
Event Delay Time (sec)
S262
Event Enabled
Event: UNIT HRS EXCEEDED
Event Delay Time (sec)
S263
Event Enabled
Event: SMOKE DETECTED
Event Delay Time (sec)
S264
Event Enabled
Event: WATER UNDER FLOOR
148
Range
‒
Disabled Enabled
MESSAGE WARNING ALARM
‒
Disabled Enabled
MESSAGE WARNING ALARM
‒
Disabled Enabled
MESSAGE WARNING ALARM
‒
Disabled Enabled
MESSAGE WARNING ALARM
‒
Disabled Enabled
MESSAGE WARNING ALARM
‒
Disabled Enabled
MESSAGE WARNING ALARM
0 - AR
1 - MR
10 - 9999 sec
Disabled Enabled
MESSAGE WARNING ALARM
10 - 9999 sec
Disabled Enabled
MESSAGE WARNING ALARM
10 - 9999 sec
Disabled Enabled
MESSAGE WARNING ALARM
10 - 9999 sec
Disabled Enabled
MESSAGE WARNING ALARM
Default
Description
Setting
‒
Enabled
Circuit 1 low pressure
ALARM
‒
Enabled
Circuit 2 low pressure.
ALARM
‒
Enabled
Circuit 1 pumpdown failure.
ALARM
‒
Enabled
Circuit 2 pumpdown failure.
ALARM
‒
Digital scroll 1 high
Enabled
temperature.
ALARM
‒
Enabled
Digital scroll 2 high
temperature.
ALARM
0 (AR)
10 sec
Electric heat high. Temp AR -
Auto Reset, MR - Manual
Enabled
Reset.
ALARM
10 sec
Enabled
Working hours exceeded.
WARNING
10 sec
Enabled
Smoke detected.
ALARM
10 sec
Enabled
Water under floor.
ALARM
Vertiv | Liebert® iCOM Installer/User Guide