Liebert® MCV Installer/User Guide 60 Hz and 50 Hz, High Density Microchannel Condenser...
Page 2
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Before proceeding with installation, read all instructions, verify that all the parts are included, and check the nameplate to be sure the voltage matches available utility power. The Vertiv™ Liebert® iCOM™ controller does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of the Liebert®...
Vertiv™ Liebert® MCV Installer/User Guide 2 Nomenclature and Components This section describes the model number for Vertiv™ Liebert® MCV units and components. 2.1 Vertiv™ Liebert® MCV Model Number Nomenclature Table 2.2 on the next page describes each digit of the 25-digit configuration number. The 14-digit model number consists of the first 10 digits and last four digits of the configuration number.
The Premium Efficiency Control board on a Vertiv™ Liebert® MCV controls EC fans on the same circuit to the same speed to maintain refrigerant head pressure in DX mode and refrigerant temperature in EconoPhase mode.
Condensers must be installed on a level surface to ensure proper refrigerant flow. • The Vertiv™ Liebert® MCV heat rejection skid cannot be installed below the evaporator. • The DA125 through DA250 are used with a Liebert® MCV heat rejection skid with receiver tanks. For this system, the outlet of the receivers on the outdoor Liebert®...
Vertiv™ Liebert® MCV Installer/User Guide 3.2 Unit Weights Table 3.2 Vertiv™ Liebert® MCV Heat Rejection Skid with Vertiv™ Liebert® EconoPhase Approximate Weights Number of Fans Number of MCV/PRE Pairs Domestic Shipping Weight Model Dry Weight, lb (kg) on Heat Rejection Skid on Heat Rejection Skid...
• Carefully inspect all items for visible or concealed damage. • Report damage immediately to the carrier and file a damage claim with a copy sent to Vertiv or to your sales representative. 4.1 Packaging Material All material used to package this unit is recyclable. Please save for future use or dispose of the material appropriately.
DPN005067 Piping Schematic XDM200/400 with Liebert® MCV 20000028 Piping Schematic with Optional Oil Separator DA250 and DA265 with Liebert® MCV without Receivers Table 5.2 Piping Arrangements Vertiv™ Liebert® MCV Condenser and Vertiv™ Liebert® EconoPhase Pump Locations Document Number Title DPN003965 Air Cooled Piping Schematic Liebert®...
Risk of oil contamination with water. Can cause equipment damage. Vertiv™ Liebert® MCV systems require the use of POE (polyolester) oil. POE oil absorbs water at a much faster rate when exposed to air than previously used oils. Because water is the enemy of a reliable refrigeration system, extreme care must be used when opening systems during installation or service.
Page 23
Refer to ASHRAE Refrigeration Handbook for general, good practice refrigeration piping. The indoor cooling unit has a factory installed high pressure safety switch in the high side refrigerant circuit. A fusible plug is installed in each Vertiv™ Liebert® DSE receiver.
Vertiv™ Liebert® MCV Installer/User Guide 5.1.2 Refrigerant Charge Requirements Table 5.6 Approximate R-410A Refrigerant Required per Circuit for Vertiv™ Liebert® MCV Heat Rejection Skid Heat Rejection Skid System No. Circuit Number Charge per Circuit with or without Receivers lb. (kg) MCV330 Single skid with (1) PRE unit (24.6)
Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power. The Vertiv™ Liebert® iCOM™ controller does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of the Liebert®...
Page 27
Vertiv™ Liebert® MCV Installer/User Guide Vertiv™ Liebert® MCV condenser power connections are provided for three phase wires and one earth ground wire. Line voltage electrical service is required for all condensers at the location of the condenser. The voltage supply to the condenser may not be the same voltage supply as required by the indoor unit.
Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power. The Vertiv™ Liebert® iCOM™ controller does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of the Liebert®...
Vertiv™ Liebert® MCV Installer/User Guide 9 Troubleshooting When an Vertiv™ Liebert® EconoPhase unit triggers an alarm, please refer to the Liebert® EconoPhase Installer/User Guide available on the product page at www.Vertiv.com. Table 9.1 Troubleshooting MCV Condenser Section Symptom Possible Cause Check or Remedy No power to condenser.
10 Control Operation The Vertiv™ Liebert® MCV Premium Efficiency Control takes about 30 seconds to boot during which time, the LED on the Premium Efficiency Control Board reads “888.” When fully booted, “F00” displays, then the value for F00. When using the control, the condenser fan(s) respond less than 5 seconds after receiving a compressor or signal from the indoor unit.
Traditional vapor compression cycle Vapor EconoPhase cycle 10.2 Overview of Operating Modes Each circuit on a system combining a Vertiv™ Liebert® EconoPhase, Vertiv™ Liebert® DSE and Vertiv™ Liebert® MCV condenser has six distinct operating modes: • Idling with compressor and pumps Off •...
Page 39
Pump Operation Flow Path on the next page. A couple of differences to note between Compressor Mode and Vertiv™ Liebert® EconoPhase operation: • The unit does not dehumidify in Liebert® EconoPhase operation. If dehumidification is desired, Liebert® EconoPhase operation must be disabled.
Compressor Solenoid valve Evaporator 10.3 Vertiv™ Liebert® EconoPhase Operation The Liebert® EconoPhase unit enables the Vertiv™ Liebert® DSE system to operate in any of three modes to control temperature, depending on the outdoor temperature and the load. • Compressor Mode •...
The third start-up routine will be the same as above. If the third start-up attempt is unsuccessful, a Pump Startup Fail alarm will be displayed and Vertiv™ Liebert® EconoPhase operation will be locked out until the user manually resets the event at the Vertiv™...
Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power. The Vertiv™ Liebert® iCOM™ controller does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of the Liebert®...
Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power. The Vertiv™ Liebert® iCOM™ controller does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of the Liebert®...
Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power. The Vertiv™ Liebert® iCOM™ controller does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of the Liebert®...
Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power. The Vertiv™ Liebert® iCOM™ controller does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of the Liebert®...
Page 77
HEAT REJECTION SKID COMPONENT LOCATION DIAGRAM MCV330 + LIEBERT® ECONOPHASE + BASE ASSEMBLY 1. Coils 2. EC Fans 3. Liebert® Econophase Pump 4. High voltage customer connection 5. Low voltage customer connection 6. Piping connections Front Note: 1. Piping connections for entire assembly are in one location (item 6).
Page 78
HEAT REJECTION SKID COMPONENT LOCATION DIAGRAM MCV330 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSEMBLY 1. MCV330 Electric Panel System 1 2. MCV330 Electric Panel System 2 3. Coils 4. EC Fans 5. Liebert® ECONOPHASE- System 1 6. Liebert® ECONOPHASE- System 2 7.
Page 79
HEAT REJECTION SKID COMPONENT LOCATION DIAGRAM MCV440 + LIEBERT® ECONOPHASE + BASE ASSEMBLY 1. Coils 2. EC Fans 3. Liebert® Econophase Pump 4. High voltage customer connection 5. Low voltage customer connection 6. Piping connections Front Note: 1. Piping connections for entire assembly are in one location (item 6).
Page 80
HEAT REJECTION SKID COMPONENT LOCATION DIAGRAM MCV440 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSEMBLY 1. MCV440 Electric Panel System 1 System 2 2. MCV440 Electric Panel System 2 3. Coils 4. EC Fans 5. Liebert® ECONOPHASE- System 1 6. Liebert® ECONOPHASE- System 2 7.
Page 81
HEAT REJECTION SKID COMPONENT LOCATION DIAGRAM MCV430 + LIEBERT® ECONOPHASE + BASE ASSEMBLY 1. Coils 2. EC Fans 3. Liebert® Econophase Pump 4. High voltage customer connection 5. Low voltage customer connection 6. Piping connections 7. 575 Volt Transformer (optional) Note: 1.
Page 82
HEAT REJECTION SKID COMPONENT LOCATION DIAGRAM MCV430 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSEMBLY System 2 System 1 Front of Unit 1. MCV430 Electric Panel System 1 2. MCV430 Electric Panel System 2 3. Coils 4. EC Fans 5. Liebert® EconoPhase System 1 6.
Page 93
LIEBERT® HEAT REJECTION SKID CABINET & ANCHOR DIMENSIONAL DATA LIEBERT® MCV430 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSEMBLY Shaded area indicates recommended clearance of 36" (914mm) for component access. System 1 System 2 Main Electrical 101 1/4" 2572mm Shaded area indicates recommended clearance of 36"...
Page 95
LIEBERT ® AIR COOLED PIPING SCHEMATIC LIEBERT® MCV WITH RECEIVERS MOUNTED ABOVE DA125-250 CIRCUIT 1 CIRCUIT 2 Notes: The outlet of the receiver must be higher than the elevation of the EEV inside the indoor unit. T he vertical height must not be greater than 60 ft (18.3 m). Unit must be trapped at bottom of riser with any rise over 5 feet (1.5m) high.
Page 96
LIEBERT ® AIR COOLED PIPING SCHEMATIC DA125-250 AND LIEBERT® MCV WITH RECEIVERS AT SIMILAR LEVELS CIRCUIT 1 CIRCUIT 2 Liebert ® MCV Condenser Unit Liebert ® Liebert ® EconoPhase Unit 44 1/2inch 1130mm Notes: DA250 with horizontal discharge should be piped out the top of unit.
Page 97
LIEBERT ® AIR COOLED PIPING SCHEMATIC ® Liebert MCV WITHOUT RECEIVERS MOUNTED ABOVE DA125-265 CIRCUIT 1 CIRCUIT 2 Notes: The bottom of the condenser coil must be no greater than 60 ft (18.3m) higher than the elevation of the EEV inside the indoor unit.
Page 98
LIEBERT ® AIR COOLED PIPING SCHEMATIC DA125-265 AND Liebert ® MCV WITHOUT RECEIVERS AT SIMILAR OR BELOW LEVELS CIRCUIT 1 CIRCUIT 2 Liebert ® MCV Condenser Unit Liebert ® EconoPhase 54 7/8" 1393mm Unit Hot Gas Discharge Hot Gas Discharge Liquid Internal EEV Height H inch ( mm) Liquid...
Page 99
LIEBERT® XDM AIR COOLED PIPING SCHEMATIC LIEBERT® MCV WITHOUT RECEIVER MOUNTED ABOVE LIEBERT® XDM CIRCUIT 1 CIRCUIT 2 Notes: 1. Single refrigerant circuit shown for clarity, for XDM400 units refrigerant connections are typical. 2. The bottom of the condenser coil must be less than 60' (18.3m) above the elevation of the EEVs inside the indoor unit.
Page 100
LIEBERT® XDM AIR COOLED PIPING SCHEMATIC LIEBERT® MCV WITHOUT RECEIVER MOUNTED BELOW LIEBERT® XDM Hot Gas Discharge Liquid Return Liebert® XDM CIRCUIT 1 CIRCUIT 2 33 1/16" 840mm Internal EEV Height 4.6m XDM200 Maximum Vertical Liquid Rise Return Liebert® MCV Condenser Unit Hot Gas Discharge...
Page 101
LIEBERT HEAT REJECTION SKID ® CABINET LIFTING POINTS LIEBERT® MCV MCV330 + LIEBERT® ECONOPHASE + BASE ASSEMBLY 13" 330mm TYP. 132 1/4" 101 1/4" 3358mm 2570mm 4" X 7" (102mm X 178mm) Lifting Points Typ. (4) Places Note: 1. Use indicated lifting points to lift the unit. Use spreader bars and/or shimmed blocks to prevent external damage. 2.
Page 105
LIEBERT HEAT REJECTION SKID ® CABINET LIFTING POINTS LIEBERT® MCV430 + LIEBERT® ECONOPHASE + BASE ASSEMBLY Front of Unit 101" 131 3/8" 2565mm 3335mm 13 7/8" 351mm TYP. 4" X 7" (102mm X 178mm) Lifting Points TYP. (4) Places Notes: 1.
Page 106
LIEBERT HEAT REJECTION SKID ® CABINET LIFTING POINTS LIEBERT® MCV430 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSEMBLY 27 3/4" 705mm TYP. 106 1/4" 2699mm Front of Unit TYP. 101" 2565mm 4" X 7" 13 7/8" (102mm X 178mm) 351mm Lifting Points TYP.
Page 107
Engineer of Record. 6. Components are not supplied by Vertiv but are required for proper circuit operation and maintenance (DA250 with top piping has internally installed traps on the discharge lines).
Page 109
LIEBERT ® PIPING SCHEMATIC LIEBERT® XDM with LIEBERT® MCV Differential LIEBERT® MCV HEAT REJECTION SKID Liebert® EconoPhase Check Valve Differential Check Valve Check Valve Liquid to Indoor Unit LIEBERT® MCV CONDENSER Solenoid Ball Valve Ball Valve Valve Hot Gas Discharge from Indoor Unit Electronic Expansion Valve...
Page 110
1. Supply and Return connections in Liebert® XDM having temperature sensor, pressure transducer, schrader air vent, and ball valve. 2. Field to install strainer in field secondary (XDM ) return line to Cooling Modules . Vertiv recommends a bypass piping arrangement to allow for cleaning the strainer without disrupting unit operation.
Page 111
1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow. 8. Vertiv requires installing external refrigerate isolation valves on the Liquid line entering and Hot Gas line leaving the indoor unit . The external isolation valves are required to allow service to safely evacuate the refrigerate charge from the indoor unit before serving the compressors, filter drier, or other refrigeration components.
Page 112
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV330 + LIEBERT® ECONOPHASE + BASE ASSY 460V & 575V LOW VOLTAGE CUSTOMER CONNECTION HIGH VOLTAGE CUSTOMER CIRCUIT 1 CIRCUIT 2 CONNECTION DETAIL B 111" 2819mm (Field Electrical Connections) 63 11/16" 1617mm 34"...
Page 113
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV330 + LIEBERT® ECONOPHASE + BASE ASSY 380V & 415V LOW VOLTAGE CUSTOMER CONNECTION HIGH VOLTAGE CUSTOMER CIRCUIT 1 CIRCUIT 2 CONNECTION DETAIL B 111" 2819mm (Field Electrical Connections) 63 11/16" 1617mm 34"...
Page 114
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV330 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSY 380V & 415V SYSTEM 1 SYSTEM 1 CIRCUIT 2 CIRCUIT 1 LOW VOLTAGE CUSTOMER CONNECTION SYSTEM 2 LOW VOLTAGE CUSTOMER CONNECTION SYSTEM 1 HIGH VOLTAGE CUSTOMER CONNECTION...
Page 115
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV330 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSY 460V & 575V SYSTEM 1 SYSTEM 1 CIRCUIT 2 CIRCUIT 1 LOW VOLTAGE CUSTOMER CONNECTION SYSTEM 2 LOW VOLTAGE CUSTOMER CONNECTION SYSTEM 1 HIGH VOLTAGE CUSTOMER CONNECTION...
Page 116
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV440 + LIEBERT® ECONOPHASE + BASE ASSEMBLY Low Voltage Customer High Voltage Customer Connection Connection Circuit 1 Circuit 2 DETAIL B (Field Electrical Connections) 111" 2819mm 34" 864mm Bottom of Box 52"...
Page 117
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV440 (2) + LIEBERT® ECONOPHASE (2) LOW VOLTAGE CUSTOMER CONNECTION + BASE ASSEMBLY SYSTEM 2 SYSTEM 1 CIRCUIT 1 SYSTEM 1 CIRCUIT 2 LOW VOLTAGE CUSTOMER CONNECTION SYSTEM 1 HIGH VOLTAGE CUSTOMER CONNECTION SYSTEM 1...
Page 118
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV MCV430 + LIEBERT® ECONOPHASE + BASE ASSEMBLY Circuit 1 Circuit 2 123 1/2" 3138mm 64 1/4" 1632mm 34" 864mm 25 3/4" 655mm Bottom of Box Bottom of Box 54 3/4" 1390mm Center of Box 87 1/2"...
Page 119
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV MCV430 + LIEBERT® ECONOPHASE + BASE ASSEMBLY Left side of Unit 72 3/4" 1847mm Front Rear of Unit of Unit 19 1/2" 497mm 15 5/8" 45 3/8" 398mm 1153mm Right side of Unit Top View Multiple customer connection locations Circuit 2...
Page 120
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV430 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSEMBLY SYSTEM 1 CIRCUIT 2 SYSTEM 1 CIRCUIT 1 123 1/2" 3138mm 64 1/4" 1632mm 34" 864mm Bottom of Box 27 3/8" 25 3/4" 696mm 655mm Bottom of Box...
Page 121
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV430 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSEMBLY Left side of Unit Main Electrical System 1 Panel Circuit 1 72 3/4" 1847mm Rear Front of Unit of Unit Main System 2 Electrical Panel Circuit 2...
Page 122
LIEBERT MCV ELECTRICAL PANEL LAYOUT MCV330 CIRCUIT 1 CIRCUIT 2 FAN 3 FAN 3 CIRCUIT 1 FAN 2 CIRCUIT 2 FAN 2 CIRCUIT 2 CIRCUIT 1 FAN 1 FAN 1 FUSES FAN CONTACTORS CONTROL BOARD CIRCUIT 1 CONTROL BOARD CIRCUIT 2 Detail A KEY ELECTRICAL DETAILS: 1) Three phase electrical service –...
Page 123
LIEBERT MCV ELECTRICAL PANEL LAYOUT MCV440 Circuit 1 Circuit 2 Fan 4 Fan 4 Circuit 1 Circuit 2 Fan 3 Fan 3 Circuit 2 Circuit 1 Fan 2 Fan 2 Circuit 1 Circuit 2 Fan 1 Fan 1 FUSES FAN CONTACTORS CONTROL BOARD CIRCUIT 1 CONTROL BOARD...
Page 124
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV330 + LIEBERT® ECONOPHASE + BASE ASSY 460V & 575V LOW VOLTAGE CUSTOMER CONNECTION HIGH VOLTAGE CUSTOMER CIRCUIT 1 CIRCUIT 2 CONNECTION DETAIL B 111" 2819mm (Field Electrical Connections) 63 11/16" 1617mm 34"...
Page 125
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV330 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSY 460V & 575V SYSTEM 1 SYSTEM 1 CIRCUIT 2 CIRCUIT 1 LOW VOLTAGE CUSTOMER CONNECTION SYSTEM 2 LOW VOLTAGE CUSTOMER CONNECTION SYSTEM 1 HIGH VOLTAGE CUSTOMER CONNECTION...
Page 126
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV330 + LIEBERT® ECONOPHASE + BASE ASSY 380V & 415V LOW VOLTAGE CUSTOMER CONNECTION HIGH VOLTAGE CUSTOMER CIRCUIT 1 CIRCUIT 2 CONNECTION DETAIL B 111" 2819mm (Field Electrical Connections) 63 11/16" 1617mm 34"...
Page 127
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV330 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSY 380V & 415V SYSTEM 1 SYSTEM 1 CIRCUIT 2 CIRCUIT 1 LOW VOLTAGE CUSTOMER CONNECTION SYSTEM 2 LOW VOLTAGE CUSTOMER CONNECTION SYSTEM 1 HIGH VOLTAGE CUSTOMER CONNECTION...
Page 128
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV440 + LIEBERT® ECONOPHASE + BASE ASSEMBLY Low Voltage Customer High Voltage Customer Connection Connection Circuit 1 Circuit 2 DETAIL B (Field Electrical Connections) 111" 2819mm 34" 864mm Bottom of Box 52"...
Page 129
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV440 (2) + LIEBERT® ECONOPHASE (2) LOW VOLTAGE CUSTOMER CONNECTION + BASE ASSEMBLY SYSTEM 2 SYSTEM 1 CIRCUIT 1 SYSTEM 1 CIRCUIT 2 LOW VOLTAGE CUSTOMER CONNECTION SYSTEM 1 HIGH VOLTAGE CUSTOMER CONNECTION SYSTEM 1...
Page 130
LIEBERT® HEAT REJECTION SKID ELECTRICAL FIELD CONNECTIONS ACCEPTABLE & UNACCEPTABLE POWER SUPPLIES FOR ALTERNATE EC FANS POWER SUPPLY REQUIREMENTS FOR 380V-575V UNITS: ACCEPTABLE: Wye Power Supply Connection PHASE A PHASE B NEUTRAL A separate neutral wire is not required to be run to the Liebert® MCV Condenser PHASE C GROUND UNACCEPTABLE:...
Page 131
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV MCV430 + LIEBERT® ECONOPHASE + BASE ASSEMBLY Circuit 1 Circuit 2 123 1/2" 3138mm 64 1/4" 1632mm 34" 864mm 25 3/4" 655mm Bottom of Box Bottom of Box 54 3/4" 1390mm Center of Box 87 1/2"...
Page 132
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV MCV430 + LIEBERT® ECONOPHASE + BASE ASSEMBLY Left side of Unit 72 3/4" 1847mm Front Rear of Unit of Unit 19 1/2" 497mm 15 5/8" 45 3/8" 398mm 1153mm Right side of Unit Top View Multiple customer connection locations Circuit 2...
Page 133
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV430 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSEMBLY SYSTEM 1 CIRCUIT 2 SYSTEM 1 CIRCUIT 1 123 1/2" 3138mm 64 1/4" 1632mm 34" 864mm Bottom of Box 27 3/8" 25 3/4" 696mm 655mm Bottom of Box...
Page 134
LIEBERT HEAT REJECTION SKID ® PRIMARY CONNECTION LOCATIONS LIEBERT® MCV430 (2) + LIEBERT® ECONOPHASE (2) + BASE ASSEMBLY Left side of Unit Main Electrical System 1 Panel Circuit 1 72 3/4" 1847mm Rear Front of Unit of Unit Main System 2 Electrical Panel Circuit 2...
Page 135
LIEBERT HEAT REJECTION SKID ® CANbus & INTERLOCK CONNECTIONS LIEBERT® MCV + LIEBERT® ECONOPHASE + BASE ASSEMBLY LIEBERT® ECONOPHASE CONTROL BOARDS (FACTORY SET) CIRCUIT 1 CIRCUIT 2 CANBUS ADDRESSING DIPSWITCH Liebert® EconoPhase CONDENSER CONTROL BOARDS (FACTORY SET) CANBUS COMMUNICATION CABLE CIRCUIT 1 TB50 CAN H...
Page 136
LIEBERT HEAT REJECTION SKID ® CANbus & INTERLOCK CONNECTIONS LIEBERT® MCV + LIEBERT® ECONOPHASE + BASE ASSEMBLY COMPONENT NOTES: 1. COMPONENT APPEARANCE, ORIENTATION, AND POSITION MAY VARY BETWEEN PRODUCT LINES. TERMINAL NAMES REMAIN CONSTANT. 2. ALL CIRCUITS TO THESE CONNECTION POINTS REMAIN CONSTANT. CAN &...
Page 137
LIEBERT® XDM CANbus & INTERLOCK CONNECTIONS LIEBERT® MCV + LIEBERT® ECONOPHASE + BASE ASSEMBLY ECONOPHASE CONTROL BOARDS (FACTORY SET) CIRCUIT 1 CIRCUIT 2 CANBUS ADDRESSING DIPSWITCH LIEBERT® ECONOPHASE UNIT CONDENSER CONTROL BOARDS (FACTORY SET) CANBUS COMMUNICATION CABLE CIRCUIT 1 LIEBERT® MCV CONDENSER TB50 CAN H OUTPUT...
Page 138
LIEBERT® XDM CANbus & INTERLOCK CONNECTIONS LIEBERT® MCV + LIEBERT® ECONOPHASE + BASE ASSEMBLY COMPONENT NOTES: 1. COMPONENT APPEARANCE, ORIENTATION, AND POSITION MAY VARY BETWEEN PRODUCT LINES. TERMINAL NAMES REMAIN CONSTANT. 2. ALL CIRCUITS TO THESE CONNECTION POINTS REMAIN CONSTANT. CAN &...
Need help?
Do you have a question about the Liebert MCV Series and is the answer not in the manual?
Questions and answers
Need dimensions and weight of Liebert MCV330E2
The Vertiv Liebert MCV330 has the following dimensions:
- Length: 132 inches (3353 mm)
- Width: 69 5/8 inches (1768 mm)
- Height: 101 inches (2565 mm)
- Service Clearance Required: 36 inches (914 mm) on all sides
The approximate weights are:
- Preliminary Assembly Weight: 3,200 lbs (1451 kg)
- Domestic Shipping Weight (Dual Skid with Receiver): 10,000 lbs (4,535 kg)
- Domestic Shipping Weight (Dual Skid without Receiver): 9,800 lbs (4,445 kg)