Specifications
General HP POD 20c specifications
Features
Overall dimensions
Weight
1
Maximum power
Power input voltage
Power input current
Maximum rack quantity
Rack Units (RU) per rack
Rack Units (RU) total
Average capacity per rack (kW)
Peak rack capacity
Voltage to rack
Minimum quantity of PDUs per HP POD 20c
Maximum quantity of PDUs per HP POD 20c
Maximum power per PDU
Network supported
1
The empty weight includes the HP POD 20c structure, empty racks, PDUs, and drop boxes. It does not include IT
equipment.
2
The maximum power depends on the exact installation and power configuration in your POD. The HP POD 20c is
electrically limited to 288 kW.
Electrical specifications
Electrical busway system information
Feature
Number of busways
Frequency
Amps (per busway)
Voltage (per busway)
Grounding
Busway configuration
2
Specification
2
60 Hz
200 A
380-415 Y
Copper
3-phase + neutral + equipment ground
Specifications
•
Height—3.05 m (10 ft)
•
Length—6.10 m (20 ft)
•
Width—2.43 m (7.97 ft)
•
Empty—7,711 kg (17,000 lb)
•
Maximum fully loaded—22,680 kg (50,000 lb)
288 kW
480 V, 3-phase, 4-wire
2 x 320 A 3-phase, 3-wire feeders
10 racks
50 RU
500 RU
30 kW
69 kW
200-240 VAC
10 (one per rack)
20 (two per rack)
30A = 17 kW; 60A = 34 kW
•
Bulk cable pass-through-fiber
•
Bulk cable pass-through-copper
•
External rated DEMARC box
Specifications 69