TM
SURFACE MOUNT DUAL SENSE MOTION SENSOR 99 190 23
1. Technical Specifications
Product type
Dual sense DALI sensor (HF and PIR, daylight harvest)
Operating voltage
120~277VAC 50/60Hz
Switched power
Maximum 20pcs devices, maximum 40mA
Power consumption
< 1W
o
Detection angle
360
Detection area (DxH)
12 x 6m (Maximum)
Mounting height
6m (Maximum)
Detection range
10% / 50% / 75% / 100%
Hold time
2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time
0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞
Stand-by dimming level
10% / 20% / 30% / 50%
Daylight threshold
50 ~ 500Lux, Disable
Warmming up time
30s
o
Operating temperature
-20
C ~ +55
Sensor mode
PIR, HF, PIR+HF, PIR / HF
3. Rotary Switch Settings
A rotary switch is built inside the sensor for
scene selection / fast programming. Total
16 channels available:
Detection
Hold
Channel
range
time
0
100%
5s
1
100%
1min
2
100%
5min
3
100%
5min
4
100%
5min
5
100%
5min
6
100%
10min
7
100%
10min
8
100%
10min
9
100%
10min
A
100%
20min
B
100%
20min
C
100%
30min
D
100%
30min
E
100%
30min
F
100%
5s
Note: settings can also be changed by remote control 99 190 27. The last action controls.
5. Functions
5.1 Daylight Harvest (Daylight Regulating)
The built-in daylight sensor can measure ambient natural light, and calculate how much electrical light is
needed to reach the target lux level. The demand is given to the LED driver by DALI signal, so as to deliver
the needed amount of electric light. The target lux level can be adjusted by remote control or long press on
the push switch.
Light level
Energy Saving Zone
0
5.2 Lux Off Function
The light dims to minimum level even switches off completelly if ambient daylight is sufficient (natural light
level exceeds target lux level), no matter it is during hold-time or stand-by time, with or without motion.
Note: if the stand-by time is preset at "+∞", the light never turns off even when natural light is sufficient.
5.3 Ambient Daylight Threshold
Switch the power supply to the sensor two times within 2 seconds, the ambient lux level is sampled and set
as the new daylight threshold / target lux level. This feature enables the daylight sensor to be commissioned
to the environment in which it is installed. Both the settings on rotary switch and the ambient lux level
sampled can overwrite each other. The last adjustment remains in memory. This may also easily be carried
out using the 99 190 27 remote control handset, please see next page (button
Art.no: 99 190 23
Installation and Instruction Manual
o
C
Rotary switch preset (Please
see the location in 2. Installation)
Stand-by
Stand-by
time
dimming level
10s
10%
5min
10%
10min
10%
+∞
10%
+∞
10%
+∞
30%
30min
10%
+∞
10%
+∞
10%
+∞
30%
1h
10%
+∞
30%
+∞
10%
+∞
30%
+∞
50%
10s
10%
Hold time
Normal Electric Light
Daylight controlled light
Stand-by time
Natural light
4 2
Time (hrs)
10
) for details.
2. Installation
Warnings:
1. Installation must be carried out by a
qualified engineer in accordance with
local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may
cause mis-triggering.
4. Ensure environmental conditions are
suitable for electronic equipment
Direct junction "J" box mounting
a. Separate control board (A) from facia (B)
& Surface box (C). C is not required.
b. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
c. Secure control board (A) to junction box.
d. Set-up sensor modes as per sections 3 & 4
of this manual.
e. Clip facial plate (B) to control board (A).
Daylight
threshold
Disable
50Lux
50Lux
Varning!
75Lux
Stäng av strömmen, ta ut säkringen på elcentralen eller ställ automatsäkringen till läge "AV", innan
100Lux
installationsarbetet påbörjas.
200Lux
Skall installeras av behörig installatör och i enlighet med gällande föreskrifter.
50Lux
75Lux
4. Sensor Mode Selection
100Lux
200Lux
Sensor mode can be easily selected by choosing the correct combination of the DIP switches
(see table below):
100Lux
200Lux
100Lux
200Lux
400Lux
100Lux
5.4 Synchronization Function
By connecting the "SYNC" terminals in parallel (see wiring diagram), no matter which sensor detects
motion, all 99 190 23 in the group will turn on the lights when surrounding natural light is below the
daylight threshold. The sensor module is shared and the detection area could be widely enlarged in
this way.
5.5 Manual Override (Push Function)
With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off the
lights manually, or adjust the target lux level. This makes the product more user-friendly and offers
more options to fit for extra-ordinary demands.
* Short push (<1s): on/off function;
ON → OFF: the light turns off immediately and cannot be lighten for a certain time (equals to hold
time preset) even movement is detected. After this period, the sensor goes back to
auto sensor mode.
OFF → ON: the light turns on and goes to auto sensor mode.
* Long push (>1s): adjust the target lux level by turning the light up or down. Both the adjustment by
* If no end-user adjustment is desired, simply leave the "push" terminal disconnected.
5.6 Semi-auto Function (Absence Detection)
The motion sensor is employed, but only activated on the manual press of the push switch. With
presence, the light remains on and can interact with ambient natural light, then dims down in
absence, eventually switching off automatically after the stand-by time has expired.
Note: end-user can choose either function 5.5 or 5.6 for application. Default function is 5.5.
5.7 8H Manual ON Mode For LED Lamp
Turn off/on the power supply three times within 3 seconds, the light will be turned on for 8 hours,
even there is no motion detected, then go back to sensor mode automatically.
Note: this 8H manual on mode can be cancelled by turning off/on the power supply one time within
1 second.
www.malmbergs.com
C - Surface box
B - Facia Cover
Infrared receiver
HF Sensor module
Rotary switch preset
Surface mount assembly
a. Separate control board (A) from facia (B) &
Surface box (C).
b. Securely mount surface box (C) to a flat and
solid surface.
c. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of
this manual.
e. Secure control board (A) to surface box (C).
f. Clip facial plate (B) to control board (A).
1 2
HF
I
PIR
II
HF+PIR
III
IV
HF/PIR
remote control and push switch can overwrite each other, the last adjustment
remains in memory.
PIR
Photocell
LED indicator
Sensor mode selection
A - Control Board
HF+PIR: Light is on when both HF
and PIR sensors are activated.
HF/PIR: Light is on when HF or PIR
sensors are activated.
2017.03.01
Need help?
Do you have a question about the Dual sense DALI 99 190 23 and is the answer not in the manual?