7.3.

SEASON CHANGEOVER

- For every season change, check that
the functioning limits lie within the
limits.
- Check that the compressor input
current is lower than the maximum
indicated in the technical data
table.
- Check, that in models with three-
phase power supply, that the
compressor noise level is not
abnormal. If this is the case, invert a
phase.
- Make sure that the voltage value
lies within the pre-fixed limits and
that unbalance between the three
phases (three-phase power supply) is
not above 3%.
7.3.1. Season changeover from panel
on machine
How to activate season changeover:
Under the On- Off branch it is possible
change the functioning mode of the
machine. In the second selection
line (can ONLY be edited if OFF was
selected in the first line) it is possible to
select the seasonal state of the heat
pump
(SUMMER, WINTER, DHW ONLY). Clearly
according to the machine configured
and according to the accessories
installed.
NOTE:
ALWAYS REFER TO THE PROCEDURE
ILLUSTRATED IN THE USE MANUAL.
7.4.

ELECTRICAL DATA

WRL / WRLH
ALIMENTATION
400V-3N-50Hz
180
230V-3-50Hz
400V-3N-50Hz
200
230V-3-50Hz
400V-3N-50Hz
300
230V-3-50Hz
400V-3N-50Hz
400
230V-3-50Hz
400V-3N-50Hz
500
230V-3-50Hz
550
400V-3N-50Hz
600
400V-3N-50Hz
650
400V-3N-50Hz
IWRLI2. 1810. 4900577_05
On-Off/ Mode
Heat Pump Unit
ON
SUMMER + DHW
Max Courrent A
Recommended Section Line
42
73
52
90
56
97
61
106
69
120
91
104
115
Main switch
10 mm²
25 mm²
10 mm²
25 mm²
100A
16 mm²
35mm²
100A
16mm²
35mm²
125A
25mm²
35mm²
125A
25mm²
100A
35mm²
125A
35mm²
125A
45A
80A
65A
65A
65A
80A
15