Page 2
Product data may be subject to modifications deemed necessary for improving the product without the obligation to give prior notice. Thank you again. AERMEC S.p.A The technical data given on the following documentation is not binding. Aermec reserves the right to apply at any time all the modifications deemed necessary for improving the product.
I-37040 Bevilacqua (VR) Italia – Via Roma, 44 Tel. (+39) 0442 633111 Telefax 0442 93730 – (+39) 0442 93566 www .aermec. com - info @ aermec. com SERIAL NUMBER EC DECLARATION OF CONFORMITY We, the undersigned, hereby declare under our own responsibility that the assembly in...
WARNINGS REGARDING THE DOCUMENTATION 1. 1 . USE IN COMPLIANCE WITH AERMEC will assume prepared staff in compliance with the THE DOCUMENTATION responsibility for damage that may national legislation effective in the country occur due to failure to comply with destination.
DESCRIPTION AND CHOICE OF UNIT The water-cooled heat pumps in the the use of exchangers with a large that already exist or new ones. VXT range with R410A refrigerant have exchange surface and a low-noise high- To exclude the risk of corrosion of the been designed and to satisfy winter/ efficiency scroll compressor.
DESCRIPTION OF COMPONENTS HYDRAULIC CIRCUIT 11 Water filter geothermic or sheet or 25 Low pressure transducer DHW Pump well water side 26 Liquid indicator DHW storage tank drain 12 Domestic hot water side water filter 27 Electric box DHW storage tank 13 User side water filter 28 PGD0 control keyboard System side expansion vessel (2lt)
DESCRIPTION OF THE COMPONENTS 6. 1 . COOLING CIRCUIT At inlet (DHW CIRCUIT) 6.4. SAFETY AND CONTROL COMPONENTS These allow to block and eliminate any The cooling circuit is contained in an impurities present in the hydraulic High pressure transducer (TAP) appropriately insulated compartment in circuits.
6.6. BASE DRAWING Geothermy Zone 1 Zone 2 Well Sheet Well Aqueduct HYDRAULIC CIRCUIT Solar heating kit heat exchanger Compressor Flow switch (ACCESSORY) Evaporator Domestic hot water instantaneous Dehydrator filter Water filters heat exchanger (DHW) Outtake gas probe •Geothermic inlet Automatic vent valve interrupted High pressure transducer •...
ACCESSORIES REMOTE PANEL MODELS PGD0 Allows basic control functioning of unit (start-up/switch-off, change function mode, alarm summary). The maximum installation distance allowed BETWEEN pCO2 and PGD0 is: • 50 m . with supplied telephone wire • • • • • •...
NOMINAL REFERENCE SOUND DATA CONDITIONS Sound power FLA = Max. Input current at full load Aermec determines sound power values with LRA = Peak current at full load HEATING: measurements taken in agreement with the 9614-2 - Condenser IN/OUT water temp.
Max. Input current at full load CONDITIONS Sound power LRA = Peak current at full load Aermec determines sound power values with HEATING: measurements taken in agreement with the 9614-2 - Condenser IN/OUT water temp. 30/35 °C Standard, in compliance with that requested by - Evaporator IN/OUT water temp.
NOMINAL REFERENCE SOUND DATA CONDITIONS Sound power FLA = Max. Input current at full load Aermec determines sound power values with LRA = Peak current at full load HEATING: measurements taken in agreement with the 9614-2 - Condenser IN/OUT water temp.
Max. Input current at full load CONDITIONS Sound power LRA = Peak current at full load Aermec determines sound power values with HEATING: measurements taken in agreement with the 9614-2 - Condenser IN/OUT water temp. 40/45 °C Standard, in compliance with that requested by Eurovent - Evaporator IN/OUT water temp.
DIMENSIONS View UPPER SIDE (HYDRAULIC CONNECTIONS) Holes for passage Electric cables Panel for Maintenance Lateral view Lateral view REAR LEFT RIGHT view Lifting Holes 209,08 235,22 58,23 1 1” F geothermal return 2 1” F geothermal flow 84,85 3 1” F system return 90,28 72,7 4 1”...
OPERATIONAL LIMITS The functioning limits diagram is relative to a ∆t on the evaporator and on the condenser of 5°C. Glycoled Standard Water Functioning Evaporator water outlet temperature °C PROJECT DATA High pressure Low pressure side side Acceptable maximum pressure Acceptable maximum temperature °C Acceptable minimum temperature...
ETHYLENE GLYCOL SOLUTIONS − The correction factors of cooling power and input power take into account FcGDpF (a) 2.20 FcGDpF (b) the presence of glycol and diverse 2. 1 0 2.00 evaporation temperatures. FcGDpF (c) 1.90 − The pressure drop correction factor FcGDpF (d) 1.80 considers the different flow rate...
EXPANSION VESSEL CALIBRATION 14. 1 . EXPANSION VESSEL CALIBRATION Standard pressure value of expansion tank when empty is 1.5 bar. Maximum value is 6 bar. Calibration of the vessel must be regulated using the maximum level difference (H) of the user (see diagram) by using the following formula: p (calibration) [bar] = H [m] / 10.2 + 0.3.
SOUND DATA To prevent the transmission of noise to Total sound levels Octave band [Hz] the heating system, it is recommended Pressure. 1000 2000 4000 8000 Power. to install VT anti-vibration mounts dB(A) Sound potential for centre of band [dB] frequency dB(A) (ACCESSORY) and flexible pipes between the VXT and the heating system.
Index Maintenance ..................37 Warnings regarding documentation ........31 26. 1 . Warnings regarding maintenance ..........37 17. 1 7. Use in compliance with destination ..........31 26.2. Extraordinary maintenance ............. 37 17.2. Preservation of the documentation ..........31 Improper use ..................38 Fundamental safety regulations ..........
Page 31
(Ministerial occur due to failure to comply with Decree 329/2004). The AERMEC VXT heat pumps water/ these instructions water are constructed according to The appliance must be installed so that the recognised technical standards 17.2.
Page 32
SAFETY WARNINGS AND INSTALLATION REGULATIONS 20.2. 1 . Safety warnings will not assume any responsibility for TO A MINIMUM. The heat pump must be installed damage due to failure to follow these All staff involved must have thorough by a qualified and suitably trained instructions.
Page 33
allow ROUTINE EXTRAORDINARY MAINTENANCE − The selected place must be such 300 mm AND FOR FUNCTIONING NEEDS. to permit laying of the necessary (fig. 5) pipes 300 mm 300 mm 500 mm 300 mm 500 mm 600 mm Fig.7. Minimum technical spacesi (for not embedded installation)
Page 34
HYDRAULIC CIRCUIT 22. 1 . HYDRAULIC CIRCUIT INSIDE according to the rules of good practice − In addition, the following are THE VXT HEAT PUMP and in compliance with the regulations necessary components of plant not in force in the country of destination supplied: The heat pump is destined to connection (Ministerial Decree 329/2004).
ELECTRIC CONNECTIONS electrical features installation It is mandatory to verify operations must be electrical lines and of the requirements refer that machine’s carried out by STAFF related components must only wiring watertight integrity IN POSSESSION OF be determined by STAFF diagram supplied with before making...
Page 36
COMMISSIONING 25. 1 . PREPARATION FOR THE HIGH PRESSURE PRESSURE COMMISSIONING 25.2. 1 . Electric controls of the live SWITCH CAN ALSO BE MANUALLY unit ATTENTION RE-ARMED THEREFORE PROCEED AS FOLLOWS IN THE PHOTO − Use a tester to verify that the value Before carrying out the controls of the power supply voltage −...
Page 37
− Before emptying place the plant different outputs and absorptions ATTENTION master switch at “OFF”: and pressure drops as indicated in If the plant contains glycol, the − Check that the loading/plant water the technical booklet. latter must not be discharged of reintegration cock is closed freely as it is a pollutant.
allow the refrigerant to escape and December 1993. cause serious damage to the unload the circuit, causing appliance compressor. The amount of refrigerant gas contai- malfunctioning. In these cases the ATTENTION ned in the plate is shown on a feature leakage points must be found and It is prohibited TO LOAD the cool- board machine...
Page 39
TABLES 29. 1 . TAB. 1 PANELLING (colour RAL 9002) Front panel screw at ¼ turn for access to the electric control board Panel with door-lock isolating switch for closure/opening of the electric panel PGD0 control panel Electric box Upper panel for inspection Upper panel Stud for VT fixing (ACCESSORY) 4 VT anti-vib.
Page 44
29.6. TAB.4 VXT M 6-8-10 WITH SOFT START AND GEOTHERMAL PUMP...
Page 45
29.7. TAV5 VXT T 6-8-10-14-16 WITH GEOTHERMAL PUMP...
Page 46
29.8. TAV6 VXT M 6-8-10 WITH SOFT START AND WELL VALVE...
Page 47
29.9. TAB.7 VXT T 6-8-10-14-16 WITH WELL VALVE...
Page 48
29. 1 0. TAB.8 Anti-interference filter Soft start As per standard on single-phase versions, according to the configurator choice for the three-phase versions Electronic control (pCO Expansion of the controller (pCO Driver for thermostatic valve Control keyboard (PGD0) Geothermal pump condensation control board Solar kit/Freecooling kit /Second zone control kit (ACCESSORY) High pressure transducer...
Page 49
29. 1 1. TAB.9 EXTERNAL AIR TEMPERATURE PROBE FOR COMPENSATION (SAE) Connect clamps 9 and 10 of the external air probe kit with respective clamps 9 -10 positioned inside the electric control board of the VXT unit. For the connection use a cable with minimum section of 0.5 mm up to 50 m. to then pass to a section of 1 mm up to100 m.
Page 50
29. 1 2. TAB. 1 0 PGD0 The pGD0 graphical display is an electronic device that allow complete management by the display of icons (defined at the level of application software). The software is only resident in the pCO. The terminal does not require any additional software during use.
Page 51
29. 1 3. TAB. 1 1 KTU ADDITIONAL MODULE FOR TEMPERATURE AND HUMIDITY CONTROL (ACCESSORY) 1 2 4 8 tLAN SERIAL Primario ADDRESS IN ANALOGICI 20VA ALIM. OUT ANAL. IN DIGITALI OUT DIGITALI Secondario +Vdc +5V GND +Vdc 14 15 H 1 2 3 230V-1Ph-N-50Hz BT10...
Page 52
29. 1 4. TAB. 1 2 KST SOLAR HEATING KIT (ACCESSORY) FU12 1 2 3 4 0 230 tLAN SERIAL Primario ADDRESS 10VA ALIM. OUT ANAL. IN DIGITALI OUT DIGITALI IN ANALOGICI FU11 Seccondario LOAD 24 0 Id1 Id2 Id3 Id4 Idc No3Nc3No4 FU13 MORSETTI PER INSTALLATORE...
Page 54
The technical data given on the following documentation is not binding. Via Roma, 44 - Tel. (+39) 0442 633111 Aermec reserves the right to apply at any time all the modifications Telefax (+39) 0442 93730 - (+39) 0442 93566 deemed necessary for improving the product...