LOCKS
3.
2
Standard Drawout Breaker Interlock
The casse es and device mobile part are equipped with a
interlock that prevents the breaker from closing unless it is in
the TEST or CONNECTED posi on. The device also opens the
main breaker contacts before the mobile part leaves and/or
approaches the CONNECTED posi on.
When the main breaker contacts are closed a second interlock
prevents inser on of the devices racking handle in to the
aperture on the casse e.
Mis Inser on device (Interlock)
An op onal device that ts into the casse e and on to the
mobile por on of a drawout breaker.
It Nprevents the inser on of a wrongly rated breaker into a
given casse e structure.
For instruc ons on how to install this device see sec on 4 of this
manual.
Door Interlock device
An op onal device that prevents the door of the equipment in
which the drawout breaker is installed to be opened when the
device is in CONNECTED posi on.
It is available in two execu ons for le
and right hinged
cabinet/panel doors. Once installed the device is always ac ve
and reacts to the posi on of the breaker in the casse e
structure.
For instruc ons on how to install this device see sec on 4 of this
manual.