AEG ME09 Installation, Operation And Maintenance Manual page 23

5000a-6400a
Table of Contents

Advertisement

BREAKER
1.
3
1.3.4 SECONDARY DISCONNECT TERMINAL BLOCKS
Breakers in Fixed Pa ern, casse es and breakers in draw out mode
are always supplied with and auxiliary connec on block with 39
connec on points (terminals) . These are easily accessible and
located at the top and front of the device.
When the number of factory installed accessories require more
than 39 connec on points needed a 2nd terminal block is
automa cally added. In cases where the accessories are mounted
in the eld
Ordering details
GSDFTR2 408030
For devices in a xed pa ern a full set of terminal blocks with 78
connec ons (Block A & B) is available as a spare..
GSDWT 408053
For devices in a drawout pa ern an addi onal terminal block
with 39 connec on points is available as a spare (BLOCK B).
-- The terminals can be used up to a ra ng of 6A at 440V AC or
6A at 250V DC. They can be used with unprepared stripped
conductors and are suited for use with conductors equipped
with spade or ring type terminals.
Schema cs and use of terminals see next page.
Assignment of terminals to accessories
-- Block A see table 1.16
-- Block B see table 1.17
-- De ni on of accessories, their labelling and use, with terminal
block connec on data see table 1.18.
²
²
²
1.3-06