A
B
3.2-04
INTRO
BREAKER
TRIP UNIT
C
LOCKS
ACCESSORIES
Ensure the xed contacts on the incoming side are isolated
prior to use the Shu er Prop Open Feature.
3.2.1 Shu er force open feature
In order to inspect the main plug in contacts within the ME09
draw out casse es a shu er force open feature is present in
each casse e.
Use
1. Remove the breakers mobile por on from the casse e.
2. Locate the shu er opera ng levers as indicated in Fig. A &
Fig. B.
3. To open the shu ers and allow access to the main contacts,
rotate the levers as indicated in Fig. C. Release the levers to re
close the shu ers.
Shu er Opera ng Lever Loca on
Shu er Opera ng Lever
TESTS