Use the type-2 frame (described earlier in this chapter under Recommended Frames for Terminal Blocks)
to design a zoned MDF that is terminating up to 16 modules. Table 7-7, Module Allocation per Zone
with Type-2 Frame, shows the number of modules allocation per zone when you design an MDF with a
type-2 frame. Each type-2 frame can accommodate 4000 jumper pairs per side. Figure 7-12, Zone
Arrangement of Type-2 Frame — Plan View, and figure 7-13, Zone Arrangement of Type-2 Frame —
Front View, Zone 2, show a type-2 frame used in a zone arrangement.

TABLE 7-7. Module Allocation per Zone with Type-2 Frame

NOTE: Custom-engineer all installations over 16 modules.
Figure 7-12. Zone Arrangement of Type-2 Frame — Plan View
MDF/lDF DESIGN: DEFINITY GENERIC 2 WITH UNIVERSAL MODULES
Number of
Number of
Modules
Zones
1
1-8
2
9
10
2
11
2
12
2
13
2
14
2
15
2
16
2
Number of
Modules for Zone
1-8
4,5
5,5
5,6
6,6
6,7
7,7
7,8
8,8
7-21