1
Insert racking shaft
2
Mount crank
3
Secure crank

23.6.6 Adjusting the contact wear indicator

- Charge the closing spring manually
 (page
- Close
6-7))
(1)
Indicator pin
(2)
Indicator pin before adjustment
(3)
Indicator pin adjusted
Using a screwdriver, cut the plastic indicator pin along the upper edge of the large recess.
If the indicator pin is no longer visible, the contact system must be replaced.
23 – 22
1
 (page 6-4)
(1)
0071-2
2
3
screwdriver
10 mm / 3/8'' blade
(2)
(3)