Check List For Commissioning - Siemens UL 1066 Operating Instructions Manual

Low voltage power circuit breaker
Table of Contents

Advertisement

6.3

Check list for commissioning

Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
Action required
Verify the circuit breaker is OPEN
Verify the rating plug is installed
Rating plug (page 9-44)
Verify the TRIP indicator is reset
Set the
trip unit
to appropriate values
Trip units (page 9-1)
Apply secondary and control voltages
Close the cubicle door
Rack circuit breaker into connected position
Push in the racking handle
Charge closing spring
Ensure the following conditions exist
Undervoltage release
Locking devices
Indicators
DANGER
energized
not activated
q
6 – 6

Hide quick links:

Advertisement