3.1.8

Anti-Condensation Heaters

Control cubicle
Operating mechanism
Table 6 Anti-condensation heaters
The anti-condensation heaters must always be
switched on.
3.1.9
Reference Contact IK-3
Principle
Fixed Hall sensor and moving magnet
Hall sensor
HE-6103
Magnet
HE-6104
Supply voltage
24VDC
Operating tempera-
-40°C ... +85°C
ture
Output
4...20 mA, CLOSE: >18 mA, OPEN: <6 mA
Resolution
<0,2 ms
Transmission
Current loop, max. 500 m
Table 7 Technical Data IK-3
3.1.10

Further Technical Data

Note
Technical Data for
-
Trip voltage
-
Control voltage
-
Heater voltage
-
Pressure monitoring for SF
-
Charging motor of the spring drive mecha-
nism
are indicated in the circuit diagram.
Note
Technical Data for
-
Circuit-breaker weights
-
the permitted cable pull F
are indicated in the dimension drawing.
90 W
210 W
6