Priming And Adjustment Of Oil Pump - Ecoflam Multicalor 170.1 PR Manual

Gas/light-oil dual burners
Table of Contents

Advertisement

Available languages

Available languages

420010243004 MULTICALOR 170.1-200.1 PR/PR
EN
Two-pipe siphon feed system
Bitubo dalla sommità del serbatoio
SUNTEC J7
1
SUNTEC
5
2
VERIFY:
- That piping system is perfectly sealed;
- That the use of hoses is avoided whenever is possible (use copper pipes preferably);
- That depression is not greater than 0,45 bar, to avoid pump's cavitation;
- That check valve is suitably designed for the duty;
The pump pressure is set at a value of 22-25 bar during the testing of burners. Before starting the burner, bleed the air
in the pump through the gauge port. Fill the piping with light-oil to facilitate the pump priming. Start the burner and
check the pump feeding pressure. In case the pump priming does not take place during the first prepurging, with a con-
sequent, subsequent lock-out of the burner, rearm the burner's lock-out to restart, by pushing the button on the control
box. If, after a successful pump priming, the burner locks-out after the prepurging, due to a fuel pressure drop in the
pump, rearm the burner's lock-out to restart the burner. Do never allow the pump working without oil for more than
three minutes.
Note: before starting the burner, check that the return pipe is open. An eventual obstruction could damage the
pump sealing device.
SUCTION LINE LENGTHS MAX. FOR TWO - PIPE SYSTEMS
H
Two-pipe lift system
Bitubo in aspirazione
H

PRIMING AND ADJUSTMENT OF OIL PUMP

SUNTEC TA....C
4
1
5
6
3
Copper pipe
H
Lunghezza tubazioni (m)
(m)
ø 14 mm
0
16
0,5
18
1
20
2
25
3
29
3,5
31
H
Copper pipe
Lunghezza tubazioni (m)
(m)
ø 14 mm
0
16
0,5
14
1
12
2
7
3
3
3,5
1
4
3
2
pag.24
To calculate the length of
the pipework all the staight
J 7
parts, curves, up and down
ø 16 mm
pipes must be taken into
29
consideration. The static
33
suction height is the
37
distance between the stan-
44
ding valve and the axis of
52
the burner pump.
55
Pressure must not exceed
0,45 bar; if pressure is
greather pump operation
may become faulty, leading
J 7
to an increase in mechani-
ø 16 mm
cal noise and perhaps even
29
breakage.
26
22
14
7
4
1 - INLET
2 - RETURN
3 - BLEED AND PRESSURE GAUGE PORT
4 - VACUUM GAUGE PORT
6
5 - PRESSURE ADJUSTMENT
6 - TO NOZZLE

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multicalor 200.1 pr

Table of Contents