Priming And Adjustment Of Oil Pump - Ecoflam Multicalor 170.1 P AB Manual

Gas/light-oil dual burners
Table of Contents

Advertisement

Available languages

Available languages

SUNTEC AJ 6 C-C
3
5
SUNTEC
SUNTEC
4
2
1
- That check valve is suitably designed for the duty;
The pump pressure is set at a value of 12 bar during the testing of burners. Before starting the burner, bleed the air in
the pump through the gauge port. Fill the piping with light-oil to facilitate the pump priming. Start the burner and
check the pump feeding pressure. In case the pump priming does not take place during the first prepurging, with a
consequent, subsequent lock-out of the burner, rearm the burner's lock-out to restart, by pushing the button on the
control box. If, after a successful pump priming, the burner locks-out after the prepurging, due to a fuel pressure drop
in the pump, rearm the burner's lock-out to restart the burner. Do never allow the pump working without oil for more
than three minutes. Note: before starting the burner, check that the return pipe is open. An eventual obstruction could
damage the pump sealing device.
NB : For one-pipe installation, the by-pass plug must be removed from the vacuum gauge port and the return port sea-
led by steel plug and washer.
(Not all model combinations are available
Consult your Suntec representative)
AJ
6
Flange mounting
000 : standard model
cut-off function
002 : by-pass nozzle
no cut-off function
003 : Ø 8 mm shaft
cut-off function
Revision number
Installation
P : by-pass plug installed
in vacuum gauge port
for two-pipe operation

PRIMING AND ADJUSTMENT OF OIL PUMP

SUNTEC J7
1
6
SUNTEC
5
2
PUMP SUNTEC AJ TECHNICAL DATA
PUMP
IDENTIFICATION
AJ : basic valve
Gear set capacity
(see pump capacity curves)
Shaft rotation
and nozzle location
(seen from shaft end)
A : clockwise rotation /
right hand nozzle.
B : clockwise rotation /
left hand nozzle.
C : anti clockwise rotation /
left hand nozzle.
D : anti clockwise rotation /
right hand nozzle.
Pressure range
C : 10-20 bars
E : 10-30 bars
C
C
1
000
4 P
420010399600 MULTICALOR 170.1 -200.1 P AB
1 - INLET
4
2 - RETURN
3 - BLEED AND PRESSURE GAUGE PORT
4 - VACUUM GAUGE PORT
5 - PRESSURE ADJUSTMENT
6 - TO NOZZLE
VERIFY:
- That piping system is perfectly sealed;
- That the use of hoses is avoided whenever
is possible (use copper pipes preferably);
6
- That depression is not greater than 0,45
3
bar, to avoid pump's cavitation;
Oil under suction
By-pass
plug
Oil under pressure
removed
By-passed oil
returned to tank
or to suction
Pressure
gauge port
Pressure
adjustment
By-pass
plug
inserted
Vacuum
gauge port
Return
Inlet
pag.25
Back
to suction
ONE PIPE
Return
INSTALLATION
plugged
To nozzle
Gear set
Tenuta
albero
TWO PIPE
INSTALLATION