AirCon Service Center
Problem
The display shows
"Error 04"
The display shows
"Error 09"
The display shows
"Error 10"
The display shows
"Error 11"
The display shows
"Error 12"
The display shows
"Error 52"
EN
Cause
It is not possible to lower the
pressure when flushing takes
place.
During the flushing process,
no pressure could be ascer-
tained at the low pressure
connection of the air condi-
tioning service unit.
During the software test, the
compressor failed to reduce
the internal pressure suffi-
ciently.
It was not possible to drain
any used oil during the soft-
ware test.
It was not possible to remove
any refrigerant from the inter-
nal tank during the software
test.
No USB stick was found/rec-
ognised
Troubleshooting
Remedy
Check air conditioner and
connections for leaks, con-
strictions and ice build-up.
Check pressure transducer
calibration.
Connect low pressure hose
to the flush container and
open valve.
Residual pressure on the
pressure gauges?
Check pressure transducer
calibration.
Check internal bottle pres-
sure.
Check the compressor and
the corresponding solenoid
valves.
Is there residual oil in the dis-
tillator, or was the draining of
used oil interrupted during
the last process?
Insert bottle for used oil cor-
rectly.
Is there a vent hole in the
used oil container/is the vent
hole clogged?
Check pressure transducer
calibration.
Check whether the tank
valve on the internal tank is
open.
Check the RE valve.
Is the ambient temperature
below 10 °C?
Insert the USB stick.
Make sure that the USB stick
has been formatted with the
FAT32 file system.