4.8

Firing rate

The burner output is chosen from within the diagram area (Fig. 3).
To ensure the burner works correctly, the start-up
should always occur within the relative firing rate.
WARNING
0.8
0.6
0.4
0.2
0
1
D7241
15
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0
- 0.2
- 0.4
40
4.8.1

Test boiler

The firing rate has been defined on test boilers according to EN
267 standard.
4.8.2

Commercial boilers

The burner-boiler combination poses no problems if the boiler
conforms to EN 303 and its combustion chamber dimensions are
similar to those provided in EN 267.
If, on the other hand, the burner is combined with a commercial
boiler that does not conform to EN 303, or where the combustion
chamber is much smaller than the dimensions set out in EN 267,
please contact the manufacturers.
20136520
Technical description of the burner
BGK1
2
20
25
30
35
BGK3
4
5
50
55
60
45
WARNING
BGK2
3
4
40
45
50
D9487
Light oil output – kg/h
6
Heat output – kW
65
75
70
10
GB
The firing rates (Fig. 3) were obtained at an ambi-
ent temperature of 20 °C, at a barometric pressure
of 1013 mbar (about 0 m a.s.l.) and with the com-
bustion head regulated as indicated on page 20.
Light oil output – kg/h
5
55
60
Heat output – kW
Fig. 3