Blue-White ProSeries SONIC-PRO S4 Series Installation And Operating Manual

Blue-White ProSeries SONIC-PRO S4 Series Installation And Operating Manual

Ultrasonic flow meter

Advertisement

Quick Links

d
SONIC-PRO
Series S4
Ultrasonic Flow Meter
Installation and Operating Manual
ProSeries
2
d
ProSeries
T WO-YEAR
WARRANTY
by Blue-White Ind.
Industries, Ltd.
Industries, Ltd.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ProSeries SONIC-PRO S4 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Blue-White ProSeries SONIC-PRO S4 Series

  • Page 1 SONIC-PRO Series S4 Ultrasonic Flow Meter Installation and Operating Manual ProSeries ProSeries T WO-YEAR WARRANTY by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 2: Safety Precautions

    QUESTIONS REGARDING THE SAFE USE OF THIS PRODUCT AND OTHER TECHNICAL ASSISTANCE MAY BE DIRECTED TO: Blue-White Industries 714-893-8529 techsupport @blue-white.com ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 3: Product Overview

    From this, the actual time-of-flights, the distance traveled in the fluid and the angle of the ultrasonic signal path, it calculates the fluid velocity. ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 4: Mounting Location

    Mounting 8.00 in [20.3 cm] The SPU can be mounted on horizontal or vertical pipe. The pipe must be secure and of sufficient strength to support the weight of the SPU. ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 5 130° F (54° C) 120° F (49° C) 110° F (43° C) 100° F (38° C) PVC Adapters 90° F (32° C) 80° F (27° C) 70° F (21° C) WORKING PRESSURE (PSI/g) ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 6: Wiring Installation

    Wiring Compartment Transducer A Transducer B Back-up Battery Compartment (4 D cells - not included) Communications Cable Grommet Optional Communications Circuitry Wiring Terminals Main PCB Connection Communications Touchpad Circuitry Connection Input Socket ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 7: Wiring Terminals

    Can be pulled up to 30V @ 10mA (3K pull-up) OUTPUT: Duty Cycle: 50%+/-5% Open Collector Frequency Range: 0-1000 Hz (-) Negative Resolution: 1 Hz Accuracy: 0.5% F.S. Blue-White model FC sensor. PADDLEWHEEL (+) Positive 100mVp-p, 10 to 350Hz SENSOR INPUT: AC Sine wave (-) Negative RELAY ‘A’ OUTPUT...
  • Page 8: Operation

    FAULT 12 - The allowable SOS (Speed Of Sound) error set-point has been exceeded. Ÿ FAULT 21 - The configuration data is not valid. Ÿ 0.28” 0” U.S Gallons/Min F-11 XDCR Disc. Error Code U.S Gallons ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 9: Menu Navigation

    Press ENTER to confirm the configuration changes have Ÿ Configuration been saved. XDCR Settings Press up arrow p to RUN. Ÿ Save Config. Press right arrow u or ENTER to enter the RUN mode, Ÿ Configuration Configuration Saved! ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 10 Enter Value 0.0000 Sign(B->A) 0.0000 Positive Pipe Wall Thick. Enter Value Negative 0.0000 Custom Pipe Material HDPE Enter Value Pipe SOS 0.0000 Custom Fluid Fluid Type Water Enter Value Fluid SOS 0000 ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 11: Transducer Menu

    25 = 25 ft cable, transducer cable model number option “B” 50 = 50 ft cable, transducer cable model number option “C” 100 = 100 ft cable, transducer cable model number option “D” Transducer Model Mount Method Cable Length(ft) Enter Value ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 12 These are factory calibration factors that should not be changed without first contacting the factory for technical assistance. Pipe Pipe Outside Dia. Enter Value 0.0000 Pipe Wall Thick. Enter Value 0.0000 Custom Pipe Material HDPE Enter Value Pipe SOS 0.0000 ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 13 Oil, Diesel 1250 68 (20) Oil, Motor (SAE 30) 1487 Oil, Mineral 77 (25) 1431 68 (20) Potassium Hydroxide 50% 2800 68 (20) Sodium Hypochlorite 12% 1835 68 (20) Sulfuric Acid 96% 1260 ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 14 FR Custom V/Gal High Fl. Cut-Off Enter Value Scaling Off-set Enter Value 1.0000 Enter Value 0.0000 Zero Off-set FR Offset Sign Positive Negative SOS Fault Window Enter Value Sleep Time(s) Enter Value ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 15 Enter Value Tot. Set Point 2 0.0000 Enter Value Tot. Set Point 3 0.0000 Enter Value Tot. Set Point 4 0.0000 Enter Value Tot. Set Point 5 0.0000 Copy Logs Delete Logs ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 16: Display Menu

    Seconds Time Units U.S. Barrels Liq. Minutes U.S. Barrels Oil Hours Cubic Feet Days Acre Feet Enter Value Imperial Gallons Fl. Rate Decimal Cubic Meters Liters Milliliters Enter Value FR Custom V/Gal ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 17 (temperature change) Fault Window or if the fluid composition changes (chemical concentration, different chemicals, etc.). The default value is 10%. The maximum allowable value is 50%. SOS Fault Window Enter Value ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 18 The sleep cycle can be interrupted by pressing the ENTER button. Data logging cannot occur while sleeping. Logging will occur if the meter is “awake” and if it is time to log data. Sleep Time(s) Enter Value ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 19 Modbus RTU Modbus TCP Ethernet Profinet None Address Profibus DPV1 Enter Value Modbus RTU Enter Value Modbus TCP IP SET 192.168.234.123 CANCEL Ethernet IP SET 192.168.234.123 CANCEL Profinet IP SET 192.168.234.123 None CANCEL ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 20 Flow rates are mapped to frequencies using a straight line through the two points specified. Pulse 0-1000 Rate at Min Freq. Enter Value 0.0000 Min Frequency Enter Value Rate at Max Freq. Enter Value 0.0000 Max Frequency Enter Value 1000 ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 21 The user must press the ESC button to clear a latched relay. Relay B None B Monitor Flow Rate High Trigger B Enter Value High Release B Enter Value Low Trigger B Enter Value Low Release B Enter Value Time(s) B Enter Value ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 22 Up to 12 Mbit/s DB9F Modbus TCP RJ45 10/100 Mbit/s full/half duplex Industrial Ethernet/IP 10/100 Mbit/s full/half duplex RJ45 Profinet IO RJ45 100 Mbit/s full duplex Communications Cable Grommet Optional Anybus Communications Module ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 23 4 to 20mA current output Reserved unsigned char Flow Frequency unsigned char Frequency output Firmware Version unsigned char 8 ASCII characters. A11.22.33 Log Entry unsigned char Log Entry String Eg: 2013/12/29 09:15:00 FR 0.0000 TL 0.00 ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 24: Global Configuration

    Restore USB Conf. Config. File Found. Erasing Config File.. Restored Config. Firmware Update Firmware Upgrade USB Drive Found. Press ESC to upgrade Change Password Change Password Old Pass.: 0000 NEW Pass.: 0000 CANCEL ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 25: Save/Restore Config

    The S4 firmware can be upgraded to the latest version. Download from www.blue-white.com to a USB flash drive. Firmware Update Configuration data will not be erased. Firmware Upgrade Firmware Update USB Drive Found. Press ESC to upgrade ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 26: Specifications

    Number of Goodness of Measurement boxes filled in Analog output value (4-20 mA) 1” 1.12 (4.24) 67.3 (255) 10. Frequency output value (0-1000 Hz) 1-1/2” 2.75 (10.4) 165 (625) 11. Firmware version 2” 4.60 (17.4) 276 (1045) ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 27: Model Number System

    F/NPT , HDPE F/NPT, 316SS Inline Body Material Polyethylene (HDPE) Sample Part Number Inline Pipe/Transducer Only Sonic-Pro Transducer Transducer Model Transducer Cable Length and Connection Type Pipe Configuration Specifications 015AG Sample Number ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 28 Page 27 Sonic-Pro 7.2 Sound speed data Water Sound Speeds Temp C Temp F Sound Speed (meters/sec) 1403 1427 1447 1481 1507 1526 1541 1552 1555 1555 1550 1543 ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 29: Dimensional Drawings

    2.75in .75" .75" [18.39cm] [16.45cm] [1.88cm] [6.99cm] [9.86cm] [18.39cm] [14.97cm] [1.88cm] [6.99cm] 7.24in 6.20in .55in 2.38in 3.50iin 7.24in 5.83in .55in 2.75in .5" .5" [18.39cm] [15.75cm] [1.39cm] [6.05cm] [8.89cm] [18.39cm] [14.80cm] [1.39cm] [6.99cm] ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 30: Menu Flow Chart

    TOT Custom V/Gal High Fl. Cut-Off Enter Value Scaling Off-set Enter Value 1.0000 Enter Value 0.0000 Zero Off-set FR Offset Sign Positive Negative SOS Fault Window Enter Value Sleep Time(s) Enter Value ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 31 Modbus RTU Enter Value Change Password Change Password Modbus TCP IP SET Old Pass.: 0000 192.168.234.123 NEW Pass.: 0000 CANCEL CANCEL Ethernet IP SET 192.168.234.123 CANCEL Profinet IP SET 192.168.234.123 None CANCEL ProSeries by Blue-White Ind. Industries, Ltd. Industries, Ltd.
  • Page 32 ! This warranty does not cover damage to the flowmeter that results from misuse or alterations, nor damage that occurs as a result of improper installation. ! Blue-White assumes no liability for the acceptability of the flowmeter in a specific application. THE USER MUST DETERMINE THE ACCEPTABILITY OF THE PRODUCT AND ITS FITNESS FOR USE IN THE SPECIFIC APPLICATION.

This manual is also suitable for:

Proseries sonic-pro s4d1ca07ag

Table of Contents