6. Automatic Heating / Cooling Control

6. Automatic Heating / Cooling Control

(
)* : FRESH AIR INTAKE MODE (Type E2)
This function is only valid as long as one indoor unit is installed within one refrigerant system or all indoor
units are controlled within a group control.
When operating in a group control, the sub-indoor units become the same operation mode of the main unit.
As for the indoor units in a group control, install them in the same air conditioning circumstances.
Use the temperature sensor which is built-in sensor of the indoor unit.
The operating mode is selected according to the set temperature and room temperature when the
operation is started.
Room temperature >
Room temperature < set temperature in remote controller – 1˚C (– 5˚C)* → Heating mode
The set temperature is corrected according to the operating mode. The correction temperature is +2
degrees in cooling mode and -2 degrees in heating mode at the time of factory shipment.
The correction value is different depending on the model. See "14. Parameter" for details.
Corrected cooling temperature – control temperature for cooling
Corrected heating temperature – control temperature for heating
When setting temperature in remote controller is 20˚C in the cooling mode (at shipment) :
Control temp. for cooling
Set temp. in remote controller
Control temp. for heating
Condition for mode change
Heating → Cooling: Room temperature > Control temperature for cooling + 0.5 degree
Cooling → Heating: Room temperature < Control temperature for heating -1.0 degree
When setting temperature in remote controller is 20˚C in the cooling mode :
Temp. for switching to cooling
+2.5deg (+5.5deg)*
Control temp. for cooling
Cooling thermostat OFF temp.
Set temp. in remote controller
Heating thermostat OFF temp.
Control temp. for heating
Temp. for switching to heating
For settings at the time of factory shipment, see "14. Parameter".
set temperature in remote controller – 1˚C (+ 5˚C)*
22˚C (25˚C)*
20˚C (20˚C)*
18˚C (15˚C)*
+2deg (+5deg)*
+1deg (+4deg)*
-1deg (-4deg)*
-2deg (-5deg)*
-3deg (-6deg)*
Heating
Heating thermostat OFF
Control Functions - Indoor Unit
Cooling
Cooling thermostat OFF
The heating
thermostat OFF
continues for 10
minutes regardless
of temp. condition.
Then, the mode
changes to cooling.
2 - 7
2WAY SYSTEM
→ Cooling mode
Heating
The cooling
thermostat OFF
continues for 10
minutes regardless
of temp. condition.
Then, the mode
changes to heating.