Way Alarm Codes - Panasonic U-8ME2E8 Service Manual & Test Run Service Manual

2way system, r410a
Table of Contents

Advertisement

3. 2WAY Alarm Codes

With types 8HP, 10HP and 12HP, only one INV compressor is supplied.
With types 14HP and 16HP, two INV compressors are supplied.
Alarm code
E06
Outdoor unit receiving failure from indoor unit
E12
Prohibit starting auto address setting
E15
Auto address alarm (A small number of indoor units)
E16
Auto address alarm (A large number of indoor units)
E20
No indoor unit during auto address setting
E24
Receiving failure of relay control unit from outdoor unit(s)
E25
Failure of outdoor unit address setting (Duplicative)
E26
Inconsistencies in number of outdoor units
E29
Failure of outdoor unit to receive relay control unit
E31
Wiring error between the P.C. board ( [L-Pow], [HIC] wire)
F04
Compressor 1 discharge temperature sensor abnormal (DISCH1)
F05
Compressor 2 discharge temperature sensor abnormal (DISCH2)
F06
Outdoor unit heat exchanger 1 gas (inlet) temperature sensor abnormal (EXG1)
F07
Outdoor unit heat exchanger 1 liquid (outlet) temperature sensor abnormal (EXL1)
F08
Outdoor temperature sensor abnormal (TO)
F12
Compressor inlet temperature sensor abnormal (SCT)
F14
Supercooling gas temperature sensor abnormal (SCG)
F16
High pressure sensor abnormal, high-load (HPS)
F17
Low pressure sensor abnormal (LPS)
F23
Outdoor unit heat exchanger 2 gas (inlet) temperature sensor abnormal (EXG2)
F24
Outdoor unit heat exchanger 2 liquid (outlet) temperature sensor abnormal (EXL2)
F31
Outdoor unit nonvolatile memory (EEPROM) error
H01
Compressor 1 abnormal current values (Overcurrent)
H11
Compressor 2 abnormal current values (Overcurrent)
H03
Compressor 1 CT sensor disconnected, short-circuit
H05
Compressor 1 discharge temperature sensor disconnected
H06
Low pressure abnormal lowering
H07
Oil loss - error
H08
Oil sensor (connection) error 1
H13
Compressor 2 CT sensor disconnected, short-circuit
H15
Compressor 2 discharge temperature sensor disconnected
H27
Oil sensor (connection) error 2
H31
Compressor 1 HIC alarm
H21
Compressor 2 HIC alarm
L04
Outdoor unit address settings duplicated
L10
Outdoor unit capacity settings not made
L17
Inconsistencies in outdoor unit models
L18
4-way valve coil disconnected, line disconnected
Alarm meaning
6 - 5
2WAY SYSTEM
Trouble Diagnosis
Page
6-7
6-7
6-7
6-8
6-8
6-8
6-9
6-9
6-9
6-9
6-10
6-10
6-11
6-11
6-12
6-12
6-12
6-13
6-14
6-11
6-11
6-14
6-14
6-14
6-15
6-15
6-16
6-17
6-17
6-15
6-15
6-17
6-18
6-18
6-19
6
6-19
6-19
6-19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-10me2e8U-12me2e8U-14me2e8U-16me2e8U-18me2e8U-20me2e8

Table of Contents