Panasonic U-8ME2E8 Service Manual & Test Run Service Manual page 43

2way system, r410a
Table of Contents

Advertisement

10. Demand Control
10. Upper Current Limitation Mode
NOTE
Since the pattern "A" and "B" perform the outdoor unit current demand control (compressor's suppressive
drive), it is easy to grasp energy saving amount.
However, it may cause the reduction of capacity in all indoor units of the same refrigerant system.
In order to make the indoor unit (group) only valid as the energy saving function where the Energy Saving
button is pressed and not to influence to other indoor units, be sure to set the outdoor unit EEPROM setting
DN18 to "1" and DN19 to "0".
(3) Serial-parallel I/O
Serial-parallel I/O must be connected in order to perform demand control.
The below input is received by serial-parallel I/O, and demand control is performed.
The demand values can be set as needed with serial-parallel I/O.
Upper current limitation setting
Contact 1
Contact 2
: Input present
* The rated current indicates the current value that is listed in the catalog or similar material.
* XX and YY are able to set in EEPROM of main outdoor unit.
EEPROM setting in main outdoor unit
CODE: 1A
Setting No.
0
40
45
100
100 (at factory shipment)
130
-1
It is able to display the present condition on the remote controller.
EEPROM setting in main outdoor unit
CODE: 1E
Setting No.
0
No display
1
Information is displayed when input of demand control is set (at factory shipment).
2
Information is displayed only when the capacity is restricted by demand control.
No control (Operates to maximum capacity)
Operates to XX% of the upper limit for the rated current.
Operates to YY% of the upper limit for the rated current.
Forced thermostat OFF setting
: Input not present
XX
0
40
45
Interval of "5"
130
No control
Control Functions - Outdoor unit
Control Functions-Outdoor Unit
Control
CODE: 1B
Setting No.
0
40
45
70
130
-1
1 - 33
2WAY SYSTEM
2WAY SYSTEM
YY
0
40
45
Interval of "5"
70 (at factory shipment)
130
No control
1