5. Inspection and Characteristics of Parts

(1) High-Pressure Switch (63PH1, 63PH2)
63PH1
Disconnect the CN69 connector (3P, white) from the outdoor unit control panel.
and
Measure the resistance between socket pins 1 and 3.
63PH2
The resistance is OK if the result is 0 Ω.
(2) Electronic Control Valve (MOV1, MOV2, MOV4)
After removing the connector from the PCB, use the following methods to check the valves.
MOV1
Measure the voltage between plug pin 5 and pins 1 through 4 at the CN64 connector (5P, white)
on the outdoor unit control PCB.
(Because of the pulse output, a simplified measurement method is used.
Set the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage
is normal.)
When the voltage is normal, measure the resistance between each pair of pins on the electronic
control valve connector.
The connector is normal if all results (pin 5 – pin 1, pin 5 – pin 2, pin 5 – pin 3, pin 5 – pin 4)
are approximately 46Ω. (If the results are 0Ω or
MOV2
Measure the voltage between plug pin 5 and pins 1 through 4 at the CN63 connector (5P, red)
on the outdoor unit control PCB.
(Because of the pulse output, a simplified measurement method is used.
Set the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage
is normal.)
When the voltage is normal, measure the resistance between each pair of pins on the electronic
control valve connector.
The connector is normal if all results (pin 5 – pin 1, pin 5 – pin 2, pin 5 – pin 3, pin 5 – pin 4)
are approximately 46Ω. (If the results are 0Ω or
MOV4
Measure the voltage between plug pin 5 and pins 1 through 4 at the CN57 connector (5P, blue)
on the outdoor unit control PCB.
(Because of the pulse output, a simplified measurement method is used.
Set the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage
is normal.)
When the voltage is normal, measure the resistance between each pair of pins on the electronic
control valve connector.
The connector is normal if all results (pin 5 – pin 1, pin 5 – pin 2, pin 5 – pin 3, pin 5 – pin 4)
are approximately 46Ω. (If the results are 0Ω or
(3) Crankcase Heater
• Check the resistance of crankcase heater using a tester.
Under the value under the temperature 20°C, the result shows 1763 ± 7% .
, replace the coil.)
, replace the coil.)
, replace the coil.)
6 - 27