Pre-Installation Checklist - Bosch DINION imager 9000 HD Installation Manual

Hide thumbs Also See for DINION imager 9000 HD:
Table of Contents

Advertisement

14
en | Planning
2.1

Pre-installation Checklist

WARNING!
This installation must be made by a qualified service person
and must conform to all local codes.
WARNING!
CSA Certified / UL Listed CLASS 2 (or Certified PoE+ rated
42.5 VDC to 57 VDC, 600 mA, 34.20 W (max), for IP models)
power adapters must be used in order to comply with
electrical safety standards.
WARNING!
Power and I/O cabling must be routed separately inside
different permanently earthed metal conduits.
WARNING!
Install external interconnecting cables in accordance with
NEC, ANSI/NFPA70 (for US application) and Canadian
Electrical Code, Part I, CSA C22.1 (for CAN application), and
in accordance with local country codes for all other countries.
CSA Certified / UL Listed CLASS 2 power adapters must be
used in order to comply with electrical safety standards.
Branch circuit protection incorporating a 20 A, 2-pole Listed
Circuit Breaker or Branch Rated Fuses are required as part of
the building installation. A readily-accessible 2-pole
disconnect device with a contact separation of at least 3 mm
must be incorporated.
1.
2.
AM18-Q0663 | 1.0 | 2013.09
www.a1securitycameras.com email: sales@a1securitycameras.com
Determine the location and distance for the junction box
based on its voltage and current consumption.
Use only UL-listed liquid tight strain reliefs for conduits to
the junction box to ensure that water cannot enter the box.
You must use 3/4 in. (20 mm) NPS watertight conduits and
fittings.
Installation manual
Available from A1 Security Cameras
DINION imager 9000 HD
Bosch Security Systems

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nai-90022-aaa

Table of Contents