Electrical Installation - Frico Sierra Original Instructions Manual

Table of Contents

Advertisement

EN
Removing the inlet grille
• Remove the screw at the lower end of the
grille.
• Pull the grille upwards to unhatch it and then
outwards to remove it.
Removing the cover panel behind the inlet grill
• Remove the 2 screws of the panel.
• Remove the panel carefully, not to damage
the sensor attached to it.
Opening the horizontal unit
To proceed with electrical connections, the
front must be removed. See the introduction
pages.
• Disconnect the power supply.
Removing the front
• Remove the screws accessible through the
outlet grill (SIFEC10/15: 2 screws, SIFEC20/25:
4 screws).
• Open the front and pull it outwards/upwards
to remove it.
Removing the inlet grille
• Pull the grille upwards to remove it.

Electrical installation

The installation, which should be preceded by
an isolator switch with a contact separation
of at least 3 mm, should only be wired by a
competent electrician and in accordance with
the latest edition of IEE wiring regulations.
The air curtain has an integrated PC board
which is connected to the selected external
control system FC. FC must be ordered
separately. FC is supplied pre-programmed.
Communication- and sensor cables are
connected to the PC board.
Should more than one air curtain be
controlled by a single FC, an additional
communication cable FCBC per unit will be
required. See manual for FC.
Vertical mounting
Control is supplied by 230V~ to the terminal
block. The PC board is accessed via cable glands
on the top or bottom of the unit. Pierce the
gland with a screwdriver before entering the
cable. If necessary, the cables can be routed
through the unit. Bundle the cables inside the
unit to prevent that they will be drawn into
the fans or get in contact with the heating
elements.
18
Sierra
For units with electrical heating, the power
supply for heating (400V3~) is connected to
the terminal block. Power and control must be
supplied separately. The electrical connection
is made on the top or bottom of the unit
depending on selection. See product key.
Connections made from below the unit
must be prepared in the floor according to
the drawing. A drilling template for the floor
is included in delivery and also available at
www.frico.net.
Horizontal mounting
The electrical connection is made on the top
of the unit. Pierce the gland with a screwdriver
before entering the cable. Control is supplied
by 230V~ to the terminal block.
For units with electrical heating, the power
supply for heating (400V3~) is connected to
the terminal block. Power and control must be
supplied separately.
The largest cable diameter for the terminal
block is 16 mm². The cable glands used must
meet the protection class requirements. In the
distribution board, it is to be indicated that "the
air curtains can be supplied from more than
one connection".
Type
Control
SIFEC10E8
SIFEC15E12
SIFEC20E16
SIFEC25E20
*) Dimensioning of external wiring shall comply with
applicable regulations and local deviations may occur.
Start-up (E)
When the unit is used for the first time or after
a long period of non-use, smoke or an odour
may result from dust or dirt which has collected
on the element. This is completely normal and
disappears after a short time.
Output Voltage
[kW]
[V]
0
230V~
8
400V3~
12
400V3~
16
400V3~
20
400V3~
Minimum
area*
[mm
]
2
1,5
2,5
4
6
10