rada 425-t3 Product Manual page 34

Table of Contents

Advertisement

Type 3 Valves
Application
The approved designations are as follows:
Model
Rada 425-t3 c
The permitted application details are:
Designation
Operating Pressure Range
-HP-B
High Pressure
-HP-S
High Pressure
High Pressure
-HP-W
-HP-T44
High Pressure
-HP-T46
High Pressure
Low Pressure
-LP-B
-LP-S
Low Pressure
-LP-W
Low Pressure
R
-LP-T44
Low Pressure
R
-LP-T46
Low Pressure
Mixed water temperature at discharge point.
R
= Rada 425-t3 approved designations.
Note! For washbasins, it is assumed that you are washing under running water.
Note! Bath fill temperatures of more than 44°C should only be available when the
bather is always under the supervision of a competent person (e.g. nurse or care
assistant).
Designation Code
LP-T44, LP-T46
Application
Bidet
Shower
Washbasin
o
Bath (44
C fill)
o
Bath (46
C fill)
Bidet
Shower
Washbasin
o
Bath (44
C fill)
o
Bath (46
C fill)
34
Mixed Water Temperature
o
38
C maximum
o
41
C maximum
o
41
C maximum
o
44
C maximum
o
46
C maximum
o
38
C maximum
o
41
C maximum
o
41
C maximum
o
44
C maximum
o
46
C maximum
°C

Advertisement

Table of Contents
loading

This manual is also suitable for:

425-t3 c

Table of Contents