Process Data - GEM 566 Operating Instructions Manual

Motorized control valve
Table of Contents

Advertisement

Available languages

Available languages

12 Specific data IO-Link (pin 6)

12.2 Process data

The motorized linear actuator has access to process data via the IO-Link. This is transmitted in cycles with every IO-Link tele-
gram.
Master → Device
Name
Drive go Open
Drive go Close
Start initialization
Locate
Setpoint analog
Device → Master
Name
Valve position Open
Valve position Close
Operating mode
Valve position analog
GEMÜ 566
Bit
0
0 → Actuator does not move into position Open
1 → Actuator moves into position Open
1
0 → Actuator does not move into position Closed
1 → Actuator moves into position Closed
2
0 → No initialization
1 → Start initialization
3
0 → Off
1 → On
8 ... 23
Setpoint in the range 0 ... 1000
Bit
0
0 → Process valve not in Open position
1 → Process valve in Open position
1
0 → Process valve not in Closed position
1 → Process valve in Closed position
2
0 → Normal operation
1 → Initialization mode
8 ... 23
Position of the valve in the range 0 ... 1000
76 / 112
Values
Values
www.gemu-group.com