ABB MTQ22-FBP Manual page 20

Softstarter type pse fieldbus plug modbus tcp
Table of Contents

Advertisement

Address for data access to de-
vice connected to port
1
2
C00h
C20h
C01h
C21h
C02h
C22h
C03h
C23h
STATUS
Approved
© Copyright 2019 ABB. All rights reserved.
Bit
3
4
C40h
C60h
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
C41h
C61h
0..15
C42h
C62h
0..15
C43h
C63h
0
1
2
3
4
SECURITY LEVEL
Public
Data
Reset possible on ac-
tive event
Software fault
Shunt fault
By-pass open
Softstarter overload
Phase loss
Bad network quality
Current loss
Fieldbus fault
Low supply voltage
High current
Motor overload
Locked rotor protec-
tion
Underload protection Current is lower than set-
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Parameter is read-
only
DOCUMENT ID.
1SFC132374M0201
F I ELD BU S CO MMU N ICAT ION
Description
Current fault or protection
can be reset
Internal fault
Current is flowing when it
should not
By-pass does not close
Too high thyristor- or heat
sink temperature
No voltage in one or more
phases on the line side
Bad network quality on
the line side
Current is not flowing
when it should
Fieldbus communication
failure
Too low control supply
voltage
Too high current
Too high motor tempera-
ture
Current is higher than set-
table value during top of
ramp
table value during top of
ramp
This bit is set if a parame-
ter write operation failed
due to the parameter be-
ing read-only.
REV.
LANG.
PAGE
B
en
20/23