ABB MTQ22-FBP Manual page 9

Softstarter type pse fieldbus plug modbus tcp
Table of Contents

Advertisement

3. Fieldbus Type
The fieldbus type parameter must be set to FbP (fieldbus plug) when using the MTQ22-FBP.
FbP is the default value of the parameter. The PSE has a built-in version of Modbus which is
activated by setting the parameter to Int (Internal).
Default value
FbP
4. Download Parameter
This parameter allows for blocking parameter download from the fieldbus. Note that down-
load of parameters works differently for different fieldbus protocols. See documentation for
the protocol used.
Default value
dPon
STATUS
Approved
© Copyright 2019 ABB. All rights reserved.
Setting range
Description
FbP/Int
FbP enables the use of external fieldbus plugs.
The Int parameter should be set when using the in-
ternal Modbus interface
Setting range
dPo/dPof
SECURITY LEVEL
Public
– When FbP is selected – configured to use
external fieldbus plug, such as the MTQ22-
FBP.
– When Init is selected – PSE will use the in-
ternal Modbus implementation to com-
municate with external devices.
It is possible to read and set this parameter
via the keypad when Fieldbus Control is set to
On or OFF.
Description
Enable/disable parameter
download
DOCUMENT ID.
1SFC132374M0201
F I ELD BU S CO MMU N ICAT ION
REV.
LANG.
PAGE
B
en
9/23