Riello PRESS 300 T/N ECO Installation, Use And Maintenance Instructions page 49

Heavy oil burners
Table of Contents

Advertisement

Available languages

Available languages

3.
INSTALLATION
3.1
FUEL OIL SUPPLY SYSTEMS
RING SUPPLY LINE
For heavy oil with viscosity up to 50°E/50°C.
1 - Cistern (heated for thick oil)
2 - Filter (with resistor for oil > 7°E/50°C)
3 - Transfer pump
4 - Control manometer
5 - Air dampers to exclude the burner (coupled)
IMPORTANT NOTES
- So that the oil can flow easily all the pipes must be properly sized, protected and heated (by electricity, steam
or hot water).
- The transfer pump capacity should be at least double of that of the burner pump.
If several burners are supplied through the same ring supply line, the transfer pump should have a capacity of
approx. 30% more than the sum of the single burners capacities.
- For starting-up: after excluding the burner by the air dampers (5) let the oil flow into the supply ring up to reach
the required circulation; after that, open the valves and supply the burner normally.
GRAVITY SYSTEM
Only for oil with viscosity up to 7°E/50°C.
Attention:
before starting up the burner, ensure that the return line is not clogged.
Any obstruction may damage the sealing of the pump.
5841
Pump priming:
loosen the cap of the vacuometer fitting
(6, fig. 1) and wait for the oil flow out.
H: Difference in height
L: Length of the suction tube
D2735
D2734
6 - Burner
7 - Pressure adjuster
8 - Filter (with resistor for oil > 7°E/50°C)
9 - Burner pump
5
GB
L metres
H
Diam.
Diam. 1
metres
1"
1/4"
0
2
10
0.5
3
11
1
4
12
1.5
5
13
2
6
14

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

632 m34390213439022

Table of Contents