Download Print this page

olympia electronics OLY-500 Quick Start Manual page 2

Maintained/non maintained emergency luminaire

Advertisement

Package Contents
1
Luminaire
1
Set of Pictograms
Mounting accessories
1
1
Manual
General
o
must not be deformed in any way (This
These luminaires are used indoors (ta 40 C) where
requirement is important to ensure the ΙΡ rating).
emergency light is needed. Each luminaire must be
3. The device must be connected to the mains
permanently connected to mains power supply. In
power supply through a circuit breaker that is
normal operation the led strip lights and the battery
depends on the total line's power load.
is charging. In case of a mains power supply
4. In case of battery replacement, it must be
failure
the
luminaire
will
light the led strip
replaced by the same type, by the manufacturer
automatically in emergency mode. When the mains
or a competent person.
power
supply
is
restored the device turns to
5. In case of inactive use for a period greater than 2
normal operation.
months, disconnect the battery by pulling out the
battery's connector.
Manual Operational Test
6. I
t i
s not allowed to discard batteries into
Remove the diffusor and then by pressing the test
common trash bins, they must be discarded
button briefly an operation test is initiated. The light
only
source and the emergency circuit of the device are
incinerate.
tested. The manual test can be conducted only if the
mains power supply and the battery are connected.
Connectors
During this test period the LAMP TEST LED will blink.
KL1: Power connector
The battery must have adequate charge. This test
CN1: Maintained, Non maintained selection
lasts for 3 seconds.
CN3: Battery connector
CN4: LED connector
Lens Removal
CN5: LED connector
When the luminaire is used without the pictograms
or the SP-1100 and you require more light output
then remove the lens that covers the LEDs.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only.
2. Always use in any case round mains cable, with a
diameter of 5-10mm (H05RN-F type 2x1mm² or
any other type, at least equal to it's mechanical
and electrical properties). ATTENTION!! The cable
Indications LED Status
CHARGE
Description
(green)
Charging
Emergency mode or
battery disconnected
Installation Instructions
1
2
3
4
1
Install the included rubber gasket and pass through the
power cables.
5
in battery recycling points. Do not
Install the included tie (if needed) to fasten
securely the power cables.
7
Battery Connection
9
Note:
This unit has replaceable batteries that can be replaced or changed by the manufacturer or a competent person.
Permanently
ON
Off
11
Commissioning
After installation, a 24 hours charging cycle must be completed, in order to achieve the nominal autonomy.
During commissioning of the luminaire write the commissioning date on the battery.
When power is applied to the unit inspect that the CHARGE indicator is steady, and that the led lamp is lit
(maintained operation) or OFF (non-maintained operation)
A full duration test should be conducted after 24 hours of continuous charging. The test is initiated by isolating
the mains power supply. Verify that the LED lamp is lit during the test period for at least the stated duration.
2
923500000_09_003
Power Connections
L
N
Ν for neutral and L for live wire.
6
Maintained
Non maintained
operation
operation
8
B
A
10
A
A
Attention!! The 6 plastic latches (A)
must be secured (click sound). This
requirement is important to ensure
the IP42 rating. Power on the
luminary.
A
A
12
923500000_09_003
Pictogram Installation
1. Fit the pictogram you need to the diffuser, be careful to
secure it on the 3 plastic holders.
1
2
2. Refit the diffusor with the pictogram.
Mounting Methods
Oly luminaires can be surface mounted on walls or ceilings. For these mounted installations, special
accessories are included.
Wall
bottom
Wall installation
view
Suspended installation with A-3018 accessory
The luminary can be installed in a suspended
ceiling.
Extra Mounting Methods *
* ATTENTION!!! The below mounting methods can be done after request of the necessary
mounting accessories!!
A
A marking panel (SP-1100) can be installed on the luminary pointing the desired direction.
A
Ceiling installation
with marking panel
Battery Replacement
It can be done only by a competent person and after the mains interruption.
1. Follow step 1 of the installation instructions and remove the diffusor.
2. Follow step 2 of the installation instructions and remove the reflector.
3. Remove the old battery and place a new one of the same type and characteristics.
4. Replace the removed parts (previous steps 1 and 2).
3
2
1
Ceiling
Ceiling installation
Suspended ceiling installation
with mounting accessory
A-3018
Suspended ceiling installation
with mounting accessories
and marking panel
923500000_09_003

Advertisement

loading