Selftesting maintained/non maintained emergency luminaire with wireless communication

Advertisement

Quick Links

Manual Test
Lens Removal
1 1
2 2
Battery Replacement
It can be done only by a competent person and after the mains interruption.
1. Follow step 1 of the installation instructions and remove the diffusor.
2. Follow step 2 of the installation instructions and remove the reflector.
3. Remove the old battery and place a new one of the same type and characteristics.
4. Replace the removed parts (previous steps 1 and 2).
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained operation (*)
A: Including test device
B: Including remote test mode
C: Including inhibiting mode
F: Automatic test gear complying with IEC 61347-2-7 denoted EL-T
60: 1 hour duration
180: 3 hours duration
480: 8 hours duration
X 1
A
B C
F
6 0
(*) Maintained operation: The luminaire lights its illumination source, when it is powered by the
mains power supply or not.
Non Maintained operation: The luminaire lights its illumination source, only in mains power supply's
failure.
ATTENTION!!!
The light source contained in this luminaire shall only be replaced by the manufacturer, or
his agent, or a similar qualified person.
NOTE!! The light source is non-user replaceable.
CAUTION : Do not view directly with bare eyes.
4
Technical Characteristics
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
SUPPLY CURRENT
U-OUT
Prated
Irated
MAX OPEN CIRCUIT VOLTAGE
WIRE CROSS SECTION
MINIMUM POWER FACTOR
BATTERY (Ni-Cd)
Tx/Rx FREQUENCY RANGE
Tx POWER
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
BATTERY PROTECTION
MIN MAX. DISCHARGE VOLTAGE
MIN MAX. DISCHARGE CURRENT
MIN MAX. CHARGE CURRENT
TRICKLE CHARGE VOLTAGE/CURRENT
MAX CHARGE VOLTAGE
INDICATIONS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
CONTROL GEAR MAX. TEMPERATURE:tc
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION (L x W x H)
WEIGHT
GUARANTEE
CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION
LED Characteristics
MANUFACTURER
MODEL NUMBER
VOLTAGE RANGE
NOMINAL POWER
CONNECTIONS
TEMPERATURE (tc)
Warranty
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty
is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which
accompanies each product. This warranty ceases to exist if the buyer does not follow the technical
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed
to them in writing. Products that have been damaged can be returned to the premises of our company for
repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
5
923102405_09_001
OLY-1024/WL
220-240V AC / 50-60Hz
4.6W / 4.8VA
19mA
22V
1h: 2W
3h: 1.6W
8h: 0.5W
1h: 176mA
3h: 146mA
8h: 45mA
22V
2
2
0.5mm - 2.5mm
0.9
3.6V/3 Ah
868-870MHz
11dBm
Basic insulation
Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3
3-4.5V
1h: 500-900mA
3h: 410-695mA
8h: 130-215mA
190-210mA
100mA
6V
LED Charge, Lamp Fault LED, Battery Fault LED
24 hours
1 h, 3 h, 8 h
4 Power LEDs
300lm / 380lm (1 h), 320lm (3 h), 100lm (8 h)
IP42
EN 60598-1, EN 60598-2-22, ΕΝ 55015,
ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
o
50 C at R18/R19
o
5 to 40 C
Up to 95%
ABS/PC, PC
270 x 147 x 48 mm
770gr.
3 years (1 year for the battery)
OLY-1024/WL
Olympia Electronics S.A.
2801205
10-12V DC
1h: 2W
3h: 1.6W
8h: 0.5W
Non reversible connection between main pcb and led module
50 °C max. across the board
www.olympia-electronics.gr
info@olympia-electronics.gr
Warranty
923102405_09_001
European
manufacturers
OLY-1024/WL
SELFTESTING
MAINTAINED/NON MAINTAINED EMERGENCY LUMINAIRE
WITH WIRELESS COMMUNICATION
Μ
NM
Duration
Light output
Non
IP42
Maintained
1h/3h/8h
maintained
380/320/100lm
Wireless
Thank you for your trust in our products
Olympia Electronics - European manufacturer

Advertisement

loading

Summary of Contents for olympia electronics OLY-1024/WL

  • Page 1 Wireless (*) Maintained operation: The luminaire lights its illumination source, when it is powered by the Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the mains power supply or not.
  • Page 2 Package Contents Installation Instructions Luminaire Mounting accessories Manual General These devices are used indoors (ta 40 C) in places is lower than the nominal, the BATTERY FAULT LED will where emergency light is needed. Each device must lit and battery needs to be replaced. If the result of the be permanently connected to mains power supply.