olympia electronics CLASSIC LIGHT Series Quick Start Manual

Self-testing maintained emergency luminaires

Advertisement

Quick Links

''CLASSIC LIGHT'' SERIES FOR SELF-TESTING MAINTAINED EMERGENCY LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
ILLUMINATION (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
Thank you for purchasing this product of
Olympia Electronics. A European manufacturer.
GENERAL
These luminaires are used indoors (ta 40 C)
where emergency light is needed.
Each luminaire must be permanently connected
to mains power supply.
In normal operation the led strip lights and the
battery is charging. In case of a mains power
supply failure the luminaire will light the led
strip automatically in emergency mode. When
the
mains
power
device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 2.
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost its
energy. During this operation the luminaire
enters the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Battery charging
The battery charging is completely controled. In
this case, is achieved the perfect
maintenance , as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance current.
Manual Test
The manual test can be conducted only if the
main power supply and the battery is connected.
By pressing the test button briefly an operation
test is initiated. During this test period all
indication LEDs are OFF.
Page 1 from 2
supply
is
restored the
battery
High Quality European based Manufacturers
GR-119/6L/42V
35-45V AC
3.6V/1.5Ah
From overcharge and full discharge
Charge, lamp fault, fault indication LED, TEST button
6 power LED's
150/300lm
EN 60598-1, EN 60598-2-22, ΕΝ 61547, EN 55015
0 to 40 C
Up to 95%
Bayblend FR3010, transparent polycarbonate
262 x 100 x 70 mm
3 years (1 year for the battery)
Automatic test
This test includes all the operations that provide
the manual test and is conducted automatically
o
every 15 days. In order to be performed, the main
power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic autonomous Test is conducted
and measures the luminaire`s back up operation.
This test is conducted automatically every six
months. In order to be performed, the main
power supply and the battery should be
connected (the battery should be charged). If the
battery is not charged, the test is postponed until
the battery is completely charged. If during the
Automatic Autonomous Test the luminaire's
duration is lower than the named, then the
battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is stated
in the list of the first page. During emergency
mode, a LED strip test is also performed.
Resetting Errors
Push the Test button for 5 seconds, to extinguish
all the indicated LED errors. Then the luminaire
enters regular operation mode.
Indication LED status (with connected mains
power supply).
AC Charge
On:
Good charge current.
Οff:
disconnected battery).
Lamp fault
4.5VA
24h
90min
IP 20
o
580gr.
No battery (No charging current or
923119004_09_004

Advertisement

loading

Summary of Contents for olympia electronics CLASSIC LIGHT Series

  • Page 1 GUARANTEE 3 years (1 year for the battery) Thank you for purchasing this product of Automatic test Olympia Electronics. A European manufacturer. This test includes all the operations that provide GENERAL the manual test and is conducted automatically These luminaires are used indoors (ta 40 C) every 15 days.
  • Page 2 Οn: faulty LED strip. In case of battery or lamp replacement, these Off: Good LED strip. must be replaced by parts of the same type, by Fault the manufacturer or by a competent person. Οff: Battery OK. 4. In case of inactive use for a period greater Blink (With AC Charge LED ON): Autonomy or than 2 months, disconnect the battery by pulling low battery problem...