4 Mounting

Suitability for the process
conditions
Switching point
Moisture
Transport
Pressure/Vacuum
10
4
Mounting
4.1

General instructions

Make sure that all parts of the instrument coming in direct contact
with the process, especially the sensor element, process seal and
process fitting, are suitable for the existing process conditions, such
as process pressure, process temperature as well as the chemical
properties of the medium.
You can find the specifications in chapter "Technical data" and on the
nameplate.
In general, OPTISWITCH 3100 C can be installed in any position. The
instrument only has to be mounted in such a way that the vibrating
element is at the height of the desired switching point.
Use the recommended cables (see chapter "Connecting to power
supply") and tighten the cable gland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cable entry. Rain and condensation water can thus drain off. This ap-
plies mainly to outdoor mounting as well as installation in areas where
high humidity is expected (e.g. through cleaning processes) or on
cooled or heated vessels.
Fig. 2: Measures against moisture ingress
Do not hold OPTISWITCH 3100 C on the vibrating element. Espe-
cially with flange and tube versions, the sensor can be damaged by
the weight of the instrument.
Remove the protective cover just before mounting
The process fitting must be sealed if there is gauge or low pressure in
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
The max. permissible pressure is specified in chapter "Technical
data" or on the type label of the sensor.
OPTISWITCH 3100 C • NAMUR