HANDLING
LIFTING THE UNIT
LIFTING SHACKLES DIMENSIONS
Use lifting shackles on each lifting lug located on each angle of the unit. Maximum diameter of the ring shaft = 20 mm
UNITS C, D, E, E+
The unit must be lifted using spacing beams to avoid the belts damages to the casing. Spacing beams must have a length equal
to the machine width – i.e. 2250 mm.
5m
Spacer Beam
UNITS F, G, H
As shown on the picture below, a lifting frame is necessary;
After lifting, withdraw angle's feet and lifting lugs.
21