FLAMMABLE GASES

POWERING UP A UNIT CONTAINING FLAMMABLE GAS

Before switching on the power supply, please carry out a refrigerant leak detection using an appropriate device to ensure that
there is no refrigerant around the machine.

ELECTRIC WIRING ON A UNIT CONTAINING FLAMMABLE GAS

When a cable passes through a wall, be sure to use a cable gland to ensure that the cable is sealed and insulated. This insulation
prevents any electric arcs that could ignite the refrigerant if leaked.

INTERVENTION ON A UNIT CONTAINING FLAMMABLE GAS

Before any intervention on a machine with A2L / A2 / A3 flammable fluid, carry out a leak detection using an appropriate device
to ensure that there is no refrigerant around the machine.
When working on a machine with flammable fluid A2L/A2/A3, do not cause sources of flammability in the area near the rooftop
(see above). For example: do not smoke, make phone calls, do not use walkie-talkies.

CORRECTIVE MAINTENANCE ON R32 GAS UNIT:

The following precautions, specific to this gas, must be taken when using the R32 refrigerant:
The vacuum pump must be fitted with a non-return valve or a solenoid valve and comply with R32 (A2L).
Pressure gauges and pipes suitable for refrigerant R32 must be used.
Use only pipe cutters and no torches to open the pipes.
The load must be applied in the liquid phase.
Always use a scale to charge the refrigerant.
Use the leak detector suitable for R32 refrigerant.
Do not use mineral oil, only synthetic oil for boring, expanding or making connections.
Keep the pipes closed before using them and pay close attention to any traces of humidity and dirt (dust, filings,
burrs, etc.).
Brazing must always be carried out in a nitrogen atmosphere.
The drill bits must always be sharp.
The refrigerant bottle must contain at least 2% of the total amount.
WARNING
Care must be taken to remove refrigerant from the system before cutting or unbrazing any piping with a tool suitable for
use with R32 (A2L).
We recommend the following protocol before any piping work:
Drain the unit with the appropriate drain device for R32 (A2L).
Charge the unit with dry nitrogen to allow any remaining R32 in the oil to be removed.
Repeat these operations twice
Release the pressure in a recovery cylinder and in accordance with the F-gas directive (R32 is an HFC listed in annex
1 of the F-gas directive).
e-BALTIC-IOM-2020.12-EN