Dimensions & weight Optional: Exhaust top connection Min. space for rotor change: A-150mm Fig.1 Model spec. Weight kg Topvex SR07 E 1000 Topvex SR09 E 1120 Topvex SR11 E 1230 1025 _____________________________________________________________________________________________________ Topvex SR07, SR09, SR11 E Installation instruction 205870...
Introduction Installation, operation and maintenance manual concerns air handling unit type Topvex SR, manufactured by Systemair AB. It consists of basic information and recommendations concerning the design, installation, start-up and operation, to ensure a proper fail-free operation of the unit.
Declaration of Conformity Manufacturer Systemair AB Industrivägen 3 SE-73930 Skinnskatteberg SWEDEN Office: +46 222 440 00 Fax: +46 222 440 99 www.systemair.com hereby confirms that the following products: Air handling units Topvex SR 07 E EL Topvex SR 07 E HWL/HWH...
Pressure transmitter 0-10V DC Pressure transmitter, control signal. Extract air Run-indication/alarm circulation pump Cooling 65-67 Free to use * These inputs may only be wired to voltage free contacts. _____________________________________________________________________________________________________ Topvex SR07, SR09, SR11 E Installation instruction 205870 Systemair AB...
Damper motor, outdoor air Damper motor, exhaust air NB! Dashed components are accessories Extract air Exhaust air Supplyair Outdoor air Drawn as a left version _____________________________________________________________________________________________________ Topvex SR07, SR09, SR11 E Installation instruction 205870 Systemair AB...
Damper motor, exhaust air value exceeds the pre-set desired value for pressure NB! Dashed components are accessories drop over the filter. Extract air Exhaust Outdoor Supply Drawn as a left version _____________________________________________________________________________________________________ Topvex SR07, SR09, SR11 E Installation instruction 205870 Systemair AB...
The unit must be duct connected or in some other way provided with protection so that it is not possible to come in contact with the fans through the duct connections. _____________________________________________________________________________________________________ Topvex SR07, SR09, SR11 E Installation instruction 205870 Systemair AB...
The illustration shows a left-handed version of the unit. Important! When reassembling the pieces make sure they are connected correctly - see cable markings on the side of the cables. _____________________________________________________________________________________________________ Topvex SR07, SR09, SR11 E Installation instruction 205870 Systemair AB...
8. Fig. 7 N.B this switch is not included. Switch for disconnection from the supply, shall have at least 3 mm contact separation in all poles. Fig. 8 ____________________________________________________________________________________________________ Topvex SR07, SR09, SR11 E Installation instruction 205870 Systemair AB...
Power consumption/currents Heater with separate power Model spec. Voltage Unit (A) Heater (kW) supply (A) Fuse (A) Topvex SR07 E HWL/HWH 400V3N~ 3x10 Topvex SR07 E EL 400V3N~ 3x10 Topvex SR07 E EL 400V3N~ *12,0 *17,5 3x25 Topvex SR07 E EL...
Communication wirings are to be connected directly to the Corrigo E28 controller (see fig.3 pos.23) on terminal 50-53 (B, A, N, E), 57-59 (Net+, Net-, Egnd) or the TCP/IP terminal. N.B. For more detailed information see the attached Corrigo E – User Manual. ____________________________________________________________________________________________________ Topvex SR07, SR09, SR11 E Installation instruction 205870 Systemair AB...
To pass a value without changing it, press RIGHT. To abort a change and return to the initial setting, press and hold the C-button until the cursor disappears. ____________________________________________________________________________________________________ Topvex SR07, SR09, SR11 E Installation instruction 205870 Systemair AB...
Set present time and date, set the control temperature and program the week schedule. Do the necessary settings for extra functions if any. Check that: - there is no unusual noise from the unit. - control panel and lamp signals are in function. ____________________________________________________________________________________________________ Topvex SR07, SR09, SR11 E Installation instruction 205870 Systemair AB...
Page 28
Systemair AB reserves the right to make changes and improvements to the contents of this manual without prior notice Systemair AB Industrivägen 3 739 30 Skinnskatteberg Phone +46 222 440 00 Fax +46 222 440 99 www.systemair.com 205870 (01-06-2011) 10-06...
Need help?
Do you have a question about the Topvex SR07 E and is the answer not in the manual?
Questions and answers