Topvex SR 09, 11, TR 09-15 Compact Air handling Units Operation and Maintenance Instructions 207880-EN_GB Document in original language 2012-11-25 A002...
Children should be supervised so that they can not play with the product. Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB...
Temp sensor exhaust air Temp sensor outdoor air 1. Only valid for units with Constant Air Volume control (CAV) 2. Only valid for units with electrical re-heater battery Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Temp sensor exhaust air Temp sensor outdoor air 1. Only valid for units with Constant Air Volume control (CAV) 2. Only valid for units with electrical re-heater battery Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
2.3.4 Temperature sensors 4 temperature sensors (PT1000) are included in the unit from factory: • Supply air sensor • Extract air sensor Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Fig. 3 Reset of the manual over heat protection in Topvex TR 09-15 and Topvex SR 09, 11 For removal of filter on TR 09-15 see chapter 5.3.1 Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB...
EL-units) Automatic fuse Automatic fuse for EL heater Contactor (K3) for control of EL heater Thermostat (EL units) Manual over heat protection reset (EL units) Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
UP or DOWN to place the cursor at the menu you wish to access and press RIGHT. If you have sufficient log on privileges the display will change to the menu you have chosen. Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions...
2222, to change default setting) Time: 12.46 Check and make sure that correct time and date is Date: 2010–03–12 displayed, if not change the settings Weekday: Friday Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 11
To enter System level use code 3333 in the “Configuration menu”. Note: To perform more advanced settings please see the separate “General Commissioning Record” on www.systemair.com, online catalogue Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Shows the status of the CO2/VOC active demand ventilation (CO2/VOC) function Never Fire damper Shows the status of the fire function damper function Not active Operation when alarm Stopped Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 13
Shows the actual supply air temperature Actual: ºC Shows the calculated supply Setp: 18ºC air set point. The exhaust air controller output signal generates the supply air controller’s set point value Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 14
Flow control Shows airflow for the extract air fan (constant airflow control) Actual: + INF Only visible if the unit is m³/h configured for Flow control Setp.: m³/h Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 15
Shows the actual external control EAF pressure and set point for the extract air fan. Actual: Only visible if the unit is Setp.: configured for "Pressure control" (VAV) Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 16
"Time in ext. Running". It's also possible to set a time here as well in order to shorten the initial set period. Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 17
Manual half speed or Manual EAF: Auto Manual set: Heating Set the heating to Auto, Manual or Off Auto Set the manual output 0-100% Manual set: 100.0 Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 18
In this menu group the settings for the activated functions are available. Depending on which choices have been made in the configuration menu some of the possible alternatives may not be displayed. Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 19
P-band: configured as Flow control 10000.0 m³/h from factory. Alternatively Pressure control if that I-time: 10.0 configuration is chosen Min. output: Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 20
Supply, Supply air control, Extract/supply air →(possible to switch between the two depending on outdoor temp.), Room/supply air →(possible to switch between the two depending on outdoor temp.), Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 21
Set the fan speed in percentage free cooling of the normal speed for each fan individually during the free SAF: 0 % cooling sequence EAF: 0 % Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 22
Set fire damper to Normally function closed/Normally open/Not active. Not active Set behaviour of the unit Operation when when fire alarm is triggered alarm Stopped/Continuous run/Normal run/Only Stopped SAF/Only EAF. Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 23
Set the cooling recovery to Yes recovery recovery or No. Set the cooling limit (the difference in temperature Cooling limit: between extract air and outdoor 2.0°C air that activates the cooling recovery). Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 24
Change password Set a new password for the password level of your choice. level:None Can only be done once logged on to the service level. New password xxxx Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Free cooling is active. The outputs Y1-Heating, Y2-Heat exchanger and Y3-Cooling are shut down. After free cooling has been activated, the heating output is blocked for 60 minutes (configurable time). Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB...
Cleaning the fans Cleaning extract louvres and supply air diffusers Cleaning the outdoor air intake Cleaning the duct system 1. Or in accordance with local rules and regulations Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
The bag filter cannot be cleaned and must be changed when necessary. New filters can be ordered from Systemair. Operation time between filter changes depends on the air pollution at the installation site. A differential pressure switch indicates when it’s time to change the filters. This will trigger an alarm in the control panel.
If the belt tension is too low it needs to be shortened. Fig. 8 Dismounting the heat exchanger Note: Make sure that the rotor motor is not exposed to moisture. Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Steel ducts can be cleaned by pulling a brush, soaked in hot soapy water through the duct via diffuser/louvre openings or special inspection hatches in the duct system (if fitted). Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions...
Press the new battery firmly down into place. Note that to preserve correct polarity, the battery can only be inserted the “right way round”. Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
OK and UP/DOWN. To abort and go back to start menu press cancel and then press LEFT. See Commissioning record for an overview of possible alarms Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB...
Before calling your service representative, make a note of the specification and production number from the type label (figure 10) Fig. 10 Type label Position Description Item number Production order number Consecutive number Production date Product code (product specification) Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 33
Topvex SR 09, 11, TR 09-15 Operation and Maintenance Instructions Systemair AB 207880...
Page 34
Systemair AB reserves the right to make changes and improvements to the contents of this manual without prior notice. Systemair AB Industrivägen 3 SE-739 30 Skinnskatteberg, Sweden Phone +46 222 440 00 Fax +46 222 440 99 www.systemair.com 207880...