YOKOGAWA FU20-FTS Instruction Manual page 15

Differential ph/orp sensor
Hide thumbs Also See for FU20-FTS:
Table of Contents

Advertisement

Remarks:
1
No revision to this drawing without prior approval of FM.
2
Installation must be in accordance with the National Electrical Code (ANSI/NFPA 70),
ANSI/ISA-RP12.06.01, and relevant local codes.
3
The sensor shall be installed to a certified intrinsically safe Smart Adapter, model
SA11-P2 with the following maximum values: Uo= 6.6 V, Io = 100 mA, Po = 165 mW.
4
The installers shall take necessary measures to prevent the possibility of sparking
resulting from differing earth potentials between the sensors and interconnecting
equipment. The sensor itself does not provide 500 V rms isolation from earth, the
interconnecting equipment Model SA11-P2 Smart Adapter however provide this
required isolation.
5
Sensor Model code:
Table 4:
Model
FU20
ab
cd
efg
h
WARNING-POTENTIONAL ELECTROSTATIC CHARGING HAZARD – SEE
6
INSTRUCTIONS
pH sensors containing accessible plastic parts and/or external conductive parts, must
be installed and used in such a way, that dangers of ignition due to hazardous
electrostatic charges cannot occur, especially in the case that the process medium is
non-conductive.
Suffix Codes
-ab-cd-efg
Connection type:
Temperature sensor
+ Region:
Type:
Option code:
Option Codes
/h
VS
Connector with ID-chip
T1
Pt1000, IS for ATEX/IECEx, FM-US,
FM-CAN
FTS PVDF body/Tapered Thread/
Dome shaped/Sodium-ions
sensitive membrane/Silicon&Viton
sealings
MTS PVDF body/Tapered Thread/
Dome shaped/Sodium-ions
sensitive membrane/FFKM&EPDM
sealings
RTS PPS body/Tapered Thread/Dome
shaped/Sodium-ions sensitive
membrane/Silicon&VITON sealings
Up to ten alphanumeric characters
(A to Z, 0 to 9 or hyphen)
15
IM 12B06J03-05EN-P

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fu20-mts

Table of Contents