5. Check the "Correction Enabled" box if you want your local transformer correction data to
be applied.
6. Click Save as... to store your setup in the device site database, and click Send to send
the setup to the device.
See the following table for available options.
Parameter
Station name
Line name
Line type
Power line length, km/mile
Parallel line length, km/mile
(Distance to transformer
branch, km/mile)
Protection trip input
Remote recorder's IP address
Remote port
Remote connection via
network
Synchronize time with remote
recorder
Power line impedance,
segments -> Setup
Parallel line mutual reactance,
Ohm/km
Transformer parameters ->
Setup
Current transformer
correction, ranges -> Setup
Options
Default
Station
0-15 characters
Power Line
0-15 characters
Single line,
Single
Parallel
(double-circuit)
line,
Transformer on
branch
0-450.00
0
0-450.00
0
External Fault Indication
None,
None
DI1-DI128
Two-ended Fault Location
0.0.0.0
1-65535
502
Ethernet,
Ethernet
GPRS/Modem
NO, YES
NO
Line Impedances
1-4
1
0-6.5000
0
Transformer on Branch
Transformer Correction
1-6
1
Description
The name of the station for fault
distance reports.
The name of the power line for fault
distance reports.
The type of the power line.
Total length of the power line.
Length of the parallel line for a line
with parallel parts, or distance to the
branch for a line with a transformer
branch.
A device digital input to which the
protection trip signal is connected.
Currently not used.
IP address of the device located at
the remote side of the line. Set it to
0.0.0.0 for single-ended fault location
calculations.
UDP port of the device located at the
remote side of the line.
The network (local or cellular) used
to communicate with the remote
device.
Enables synchronization of the local
time with the remote device clock.
Do not use with a cellular network.
The number of line segments with
different impedances. Click Setup on
the right to configure segment
impedances.
Mutual reactance between the
parallel lines.
Parameters of the power transformer
on the line branch. Click Setup on the
right to configure the transformer
parameters.
The number of correction points
within the transformer's current
rating. Click Setup on the right to
configure transformer ratio correction
factors and phase angle errors.