1.5 Transformer Inaccuracies

The time skew of voltage and current signals contribute large into inaccuracy of distance
calculations. This especially concerns customer instrument transformers that may introduce
significant phase errors. To minimize the effect of the transformer inaccuracies, follow the
instructions below:
1. The device's input voltage and current transformers are carefully calibrated at the
factory. In the event the device is provided with a 200-amps DFR module, use it only
with the supplied current transformers. Connect the transformers to the input terminals
according to the phase marking labels.
2. Use the device transformer correction setup to provide information on customer
instrument transformers' errors.
3. If your instrument transformers have significantly non-linear angle error response, use
the fault locator transformer correction setup to provide information on transformers
phase errors over the entire measurement range.