1.2 Installing the stove

The stove is heavy and therefore it is strongly recommended that when lifting, it is under-
taken by two people.
Morsø 2B Standard radiant weighs 61 kg.
Morsø 2B Standard convection weighs 76 kg.
The stove and chimney installations MUST comply to all current National and Local Building Regu-
lations; your approved Morsø dealer or your local building control officer can advise regarding this.
Ultimately, it is you and your installer who is responsible that the installation complies.
1.3 Chimney Sweeping
It may also be wise to consult your local chimney sweep before installing the stove. After your
stove has been installed, it is advisable to have the chimney checked and swept at least once a
year. In any case, if your chimney has not been used for some time, it should be inspected for
cracking, bird nests, etc. before it is put back into use.
1.4 Stove placement/clearance requirements
Minimum Clerarance requirements apply if the stove is placed near to combustible materi-
als. Permitted clearances to combustible materials are also indicated on the data plate on
the rear of the stove.
Minimum distances from flammable material:
Type of stove
2B Standard radiant
uninsulated pipe
2B Standard convection
uninsulated pipe
22
Material:
2B Standard radiant
B
Rev.
Revisions
Title:
Construction:
Afstand til brandbar væg
Released:
Format:
Distance to combustible wall
Behind the stove (A)
400 mm
300 mm
Sign.:
Date:
RSV
10.12.2009
A4
Material:
To the sides of the
stove (B)
850 mm
400 mm
B
Rev.
Revisions
Title:
Construction:
Afstand til brandbar væg
Released:
Format:
Distance to combustible wall
Sign.:
Date:
RSV
10.12.2009
A4