TZIDC-200, TZIDC-210, TZIDC-220 DIGITAL POSITIONER | 42/18-85-EN REV. E
Operating modes
Selection from the operating level:
1. Press and hold down MODE.
2. Also press and release rapidly as often as required. The
selected operating mode is displayed.
3. Release MODE.
The position is displayed in % or as a rotation angle.
Operating mode
Mode indicator
1.1
Positioning with fixed set
point.
Adjust set point by using
or .
1.2
Manual adjustment * in
the operating range.
Adjust with or **
1.3
Manual adjustment *
within the sensor range.
Adjust with or **
*
Positioning not active.
** For high-speed mode, press and simultaneously.
Position indicator
M10906b
Standard automatic adjustment
Note
Standard Auto Adjust does not always result in optimum control
conditions.
Standard automatic adjustment for linear actuators*
1. MODE Press and hold until ADJ_LIN is displayed.
2. MODE Press and hold until the countdown ends.
3. Release MODE; this starts Autoadjust.
Standard automatic adjustment for rotary actuators*
1. ENTER Press and hold until ADJ_ROT is displayed.
2. ENTER Press and hold until the countdown ends.
3. Release ENTER; this starts Autoadjust.
If Autoadjust is successful, the parameters will be stored
automatically and the positioner will revert to operating mode
1.1.
If an error occurs during Autoadjust, the process will be
terminated with an error message.
Perform the following steps if an error occurs:
1. Press and hold down operating button or for
approximately three seconds.
The unit will switch to the operating level, mode 1.3 (manual
adjustment within the measuring range).
2. Check mechanical mounting in accordance with Mechanical
mounting on page 23 and repeat the standard automatic
adjustment.
*
The zero position is determined automatically and saved during standard
automatic adjustment, counter-clockwise (CTCLOCKW) for linear actuators
and clockwise (CLOCKW) for rotary actuators.
39