TZIDC-200, TZIDC-210, TZIDC-220 DIGITAL POSITIONER | 42/18-85-EN REV. E
Special conditions
Devices must only be connected to circuits in zone 2 if they
are suitable for operation in zone 2 potentially explosive
atmospheres and for the conditions prevailing at the
installation location (manufacturer's declaration or
certificate from an inspection authority).
For the 'Limit monitor with proximity switches' circuit,
measures outside of the device must be implemented to
prevent the rated voltage from being up-scaled by more than
40 % due to transient disturbances.
It is only permissible to connect, disconnect, and switch live
circuits during installation or maintenance, or for the
purpose of carrying out repairs. Note: It is considered very
unlikely that a potentially hazardous atmosphere would be
present in zone 2 at the same time that installation or
maintenance or repair work was being carried out.
Only non-flammable gases must be used for pneumatic
power supply.
Only suited cable entries must be used that meet the
requirements of EN 60079-15.

FM / CSA

FM Approvals
TZIDC-220 Positioner, Model V18350-a014b3cd4ef
IS/I,II,III/1/ABCDEFG/T6,T5,T4
Ta = 40 °C, 55 °C, 85 °C-901265 Entity, FISCO
Entity and FISCO Parameters
Terminals
Type
Groups
+11 / −12
Entity
FISCO
FISCO
+51 / −52
Entity
+41 / −42
Entity
Parameters
A-G
U
= 24 V
max.
I
= 250 mA
max.
P
= 1.2 W
i
A-G
U
= 17.5 V
max.
I
= 360 mA
max.
P
= 2.52 W
i
C-G
U
= 17.5 V
max.
I
= 380 mA
max.
P
= 5.32 nF
i
A-G
U
= 16 V
max.
I
= 20 mA
L
max.
A-G
U
= 16 V
max.
I
= 20 mA
L
max.
NI/I/2/ABCD/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
S/II,III/2/EFG//T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
Enclosure type 4x
a
Case/mounting – 1, 2, 3, 4, 5 or 6
b Output/safe protection – 1, 2, 3 or 4
c
Option modules – 0 or 5
d Optional mechanical kit for digital position feedback –
0, 1 or 2
e
Design (varnish/coding) – 1 or 2
f
Device identification label – 0, 1 or 2
TZIDC-220 Positioner, Model V18350-a012b3cd4ef
XP/I/2/CD/T6, T5, T4 TA = 82 °C
DIP/II, III/2/FG/T6, T5, T4 Ta = 82 °C
Enclosure type 4x
a
Case/mounting – 1, 2, 3, 4, 5 or 6
b Output/safe protection – 1, 2, 3 or 4
c
Option modules – 0 or 5
d Optional mechanical kit for digital position feedback –
0, 1 or 2
e
Design (varnish/coding) – 1 or 2
f
Device identification label – 0, 1 or 2
CSA Certification 1555690
Explosion proof; enclosure 4X
Temperature range: −40 to 85 °C
T5, max. 85 °C ; T6, max. 70 °C
CL I; Div 1; Grp. C-D
CL II; Div 1; Grp. E-F-G
CL III
See FM installation drawing No. 901265 on page 63.
C
= 2.8 nF
i
L
= 7.2 µH
i
C
= 2.8 nF
i
L
= 7.2 µH
i
C
= 2.8 nF
i
L
= 7.2 µH
i
C
= 60 nF
i
= 100 µH
i
C
= 60 nF
i
= 100 µH
i
19