TZIDC-200, TZIDC-210, TZIDC-220 DIGITAL POSITIONER | 42/18-85-EN REV. E
IECEx – 'Ex i' type of protection
Ex marking
Marking
Type Examination Test Certificate
Type
Standards
Temperature Data
Temperature class
T4
T6*
*
When using the 'Limit Monitor' plug-in module in temperature class T6, the
maximum permissible ambient temperature range is −40 to 35 °C
(−40 to 95 °F).
Electrical Data
In intrinsically safe explosion protection types Ex ib IIC / Ex ia IIC,
only for connection to a certified intrinsically safe circuit.
Current circuit (terminal)
Signal circuit
(+11 / −12)
Contact input
(+81 / −82)
Switch output
(+83 / −84)
Local communication interface
(LCI)
Ex ia IIC T6 or T4 Gb
Ex ib IIC T6 or T4 Gb
IECEx TUN 04.0015X
IEC 60079-11
IEC 60079-15
Ambient temperature Ta
−40 to 40 °C *
Electrical information (maximum values)
U
= 30 V
i
I
= 320 mA
L
= negligibly small
i
i
P
= 1.1 W
i
U
= 30 V
i
I
= 320 mA
L
= negligibly small
i
i
P
= 1.1 W
i
U
= 30 V
i
I
= 320 mA
L
= negligibly small
i
i
P
= 500 mW
i
Only for connection to a programming device
outside the hazardous area (see special
The following modules may be operated as an option:
Current circuit (terminal)
Plug-in module for digital
position feedback
(+51 / −52)
(+41 / −42)
TCIDC-200
Plug-in module for analog
IEC 60079-0
position feedback
(+31 / −32)
Special conditions
•
Devices must only be connected to circuits in zone 2 if they
are suitable for operation in zone 2 potentially explosive
atmospheres and for the conditions prevailing at the
−40 to 85 °C
installation location (manufacturer's declaration or
certificate from an inspection authority).
•
For the 'Limit monitor with proximity switches' circuit,
measures outside of the device must be implemented to
prevent the rated voltage from being up-scaled by more than
40 % due to transient disturbances.
•
It is only permissible to connect, disconnect, and switch live
circuits during installation or maintenance, or for the
purpose of carrying out repairs. Note: It is considered very
unlikely that a potentially hazardous atmosphere would be
present in zone 2 at the same time that installation or
maintenance or repair work was being carried out.
C
= 6.6 nF
•
Only non-flammable gases must be used for pneumatic
i
power supply.
•
Only suited cable entries must be used that meet the
requirements of EN 60079-15.
C
= 4.2 nF
i
•
The local communication interface (LCI) for the TZIDC and
the TZIDC-200 may only be operated at U
the hazardous area.
C
= 4.2 nF
i
conditions).
Electrical information (maximum values)
U
= 30 V
Ci = 3.7 nF
i
I
= 320 mA
Li = negligibly small
i
P
= 500 mW
i
U
= 30 V
Ci = 6.6 nF
i
I
= 320 mA
Li = negligibly small
i
P
= 1.1 W
i
≤ 30 V GS outside
m
11