TZIDC-200, TZIDC-210, TZIDC-220 DIGITAL POSITIONER | 42/18-85-EN REV. E
... 2 Use in potentially explosive atmospheres
... TZIDC-210 – Ex relevant specification
IECEx – 'Ex i' type of protection
Ex marking
Marking
Type Examination Test Certificate
Shown as
Type
Standards
Temperature Data
Temperature class
T4
T6*
*
When using the plug−in module for 'Digital Feedback' in Temperature Class
T6,the maximum permissible ambient temperature range is −40 to 35 °C
(−40 to 95 °F).
Electrical data for ia/ib/ic for groups IIB/IIC
With the intrinsically safe Ex i IIC type of ignition protection, only
for connection to a certified FISCO power supply unit or a
barrier, i.e., a power supply unit with maximum values according
to the following table
Current circuit (terminal)
Signal circuit
(+11 / −12)
Ex ia IIC T6 or T4 Gb
IECEx TUN 04.0015X
TZIDC-210
IEC 60079-0
IEC 60079-11
Ambient temperature Ta
−40 to 85 °C
−40 to 40 °C*
Electrical information (maximum values)
U
= 24 V
i
I
= 250 mA
L
i
P
= 1.2 W
Characteristic curve =
i
Special conditions
The local communication interface (LCI) may only be
operated at U
atmosphere.
Devices must only be connected to circuits in zone 2 if they
are suitable for operation in zone 2 potentially explosive
atmospheres and for the conditions prevailing at the
5
installation location (manufacturer's declaration or
certificate from an inspection authority).
For the 'Mechanical digital feedback' circuit, measures
outside of the device must be implemented to prevent the
rated voltage from being up-scaled by more than 40 % due
to transient disturbances.
It is only permissible to connect, disconnect, and switch live
circuits during installation or maintenance, or for the
purpose of carrying out repairs. Note: It is considered very
unlikely that a potentially hazardous atmosphere would be
present in zone 2 at the same time that installation or
maintenance or repair work was being carried out.
Only non-flammable gases must be used for pneumatic
power supply.
Only suited cable entries must be used that meet the
requirements of EN 60079-15.
C
< 5 nF
i
< 10 μH
i
linear
≤ 30 V GS outside the potentially explosive
m